Zero-Energy Sag Corrector With Reduced Device Count
Authors:
- 12 June 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 24 (6) , 1646-1653
Abstract
Voltage sags are the leading cause of unscheduled downtime in industrial plants with high levels of automation. Zero-energy sag correctors (ZESCs) that utilize energy from those phases that have sufficient remaining voltage on them promise levels of protection that are comparable with conventional energy storage based sag correctors, but in a more compact package. This paper presents a ZESC topology with reduced device count using readily available device packages that can realize similar performance as the original ZESC circuit. The proposed ZESC behaves like a ldquothin AC converter,rdquo and can be integrated with existing assets such as transformers and switchgears. This paper presents details of the operation, design, and experimental results for such a ZESC circuit.Keywords
This publication has 10 references indexed in Scilit:
- Zero Energy Sag Correctors - Optimizing Dynamic Voltage Restorers for Industrial Applications2007
- A Voltage Sag Supporter Utilizing a PWM-Switched AutotransformerIEEE Transactions on Power Electronics, 2007
- Zero Energy Storage Voltage Sag Correctors for Industrial Applications2007
- A Detailed Comparison of System Topologies for Dynamic Voltage RestorersIEEE Transactions on Industry Applications, 2005
- Equipment failures caused by power quality disturbances2004
- A Grid Information Resource for Nationwide Real-Time Power MonitoringIEEE Transactions on Industry Applications, 2004
- Design of a versatile three-phase AC line conditioner2002
- Comparative evaluation of PWM AC-AC converters2002
- Application of a boost AC-AC converter to compensate for voltage sags in electric power distribution systems2002
- Dynamic sag correctors: cost-effective industrial power line conditioningIEEE Transactions on Industry Applications, 2001