Dynamic features of DC flashover on polluted insulators
- 1 January 2007
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 1 (1) , 8-12
Abstract
In the existing literature dealing with flashover simulation or theoretical studies, the discharge is considered to have a tubular form of uniform diameter, and its evolution is simply its foot displacement at the surface of the pollution or of the ice, while it maintains its tubular form. After presentation of the equivalent electric circuit for flashover simulation, an experimental study is presented, the purpose of which is to determine the difference between the theoretical dynamic features of flashover, based on the tubular-formed discharge assumption, and the real dynamic features. The results clearly confirm the difference between the two groups of dynamic features and that the theoretical dynamic features are the sum of the static points.Keywords
This publication has 4 references indexed in Scilit:
- Electrical contact between a local discharge on an electrolytic solution and the solution surface [wet polluted insulators]IEEE Transactions on Dielectrics and Electrical Insulation, 2000
- Dc Interfacial Breakdown on Contaminated Electrolytic SurfacesIEEE Transactions on Electrical Insulation, 1984
- Flashover of a Liquid Conducting Film Part 1: Flashover VoltageIEEE Transactions on Electrical Insulation, 1982
- Flashover Mechanism of High Voltage InsulatorsIEEE Transactions on Power Apparatus and Systems, 1979