Leading experts in transformer noise control have long warned that the acoustic impact of DC bias from HVDC converters on nearby AC transformers is more severe than the magnetizing current increase alone would suggest, because the asymmetric flux excursion activates magnetostrictive strain at even harmonics of the power frequency that the unbiased core does not produce. This research measured the A-weighted acoustic noise emitted by single-sheet and stacked-core samples of three grain-oriented electrical steel grades conventional grain-oriented (CGO), high-permeability (HiB), and domain-refined under controlled DC bias levels from 0 to 20 A/m at the Coimbra Foundation for Electromagnetic Research, Portugal, between March and October 2024. A total of 240 measurement points (3 grades × 10 DC bias levels × 8 repetitions) were captured in an anechoic chamber using a calibrated sound level meter at 0.3 m from the sample surface. The noise level rose from 38.2 dBA at zero bias to 82.1 dBA at 20 A/m for HiB steel, from 41.6 to 96.3 dBA for CGO, and from 36.4 to 70.4 dBA for domain-refined material. The WHO night-time noise guideline of 55 dBA was exceeded at DC bias levels of 8 A/m (CGO), 10 A/m (HiB), and 15 A/m (domain-refined). Domain-refined steel produced 14-26 dBA less noise than CGO across all bias levels, confirming its suitability for transformers installed near HVDC converter stations. The dominant noise frequency shifted from 100 Hz (second harmonic of 50 Hz) at zero bias to a broader spectrum including 50 Hz and 150 Hz components under DC bias, consistent with the excitation of odd-order magnetostrictive strain by the asymmetric flux waveform.