$\alpha \alpha \beta$-Based Fast and Accurate Frequency and ROCOF Measurement in Power Systems
- 8 August 2025
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Informatics
- Vol. 21 (11) , 8770-8778
Abstract
The frequency and rate of change of frequency (ROCOF) signals acquired from phasor measurement units (PMUs) are instrumental in the security monitoring and feedback control of power grids, necessitating minimal response time and high precision. Existing algorithms rarely achieve a simultaneous balance between superior noise filtering performance and rapid response time when measuring frequency and ROCOF. To address this problem, this article introduces an innovative algorithm that integrates $\alpha \beta \gamma$ series filters. The proposed algorithm leverages an $\alpha \alpha \beta$ (aab) filter, which combines an $\alpha$ filter and an $\alpha \beta$ filter, and the reference P-class PMU algorithm from the IEC/IEEE 60255.118.1-2018 standard file. By providing an original mathematical modeling approach to aab parameter acquisition, this filter effectively amalgamates the advantages of the two foundational filters. Extensive experimental simulations demonstrate that our proposed algorithm has exceptional performance across various metrics of frequency and ROCOF measurement, achieving results that compare favorably with other advanced algorithms.Keywords
Funding Information
- National Natural Science Foundation of China (U24A20258)
- National Natural Science Foundation of China (92367205)
This publication has 30 references indexed in Scilit:
- Gaussian Filters for P Class PMUs: a Performance Comparison of Alternative FIR Design Procedures2022
- Compressive Sensing Taylor-Fourier and Windowing Approach for Synchronized Phasor, Frequency and ROCOF Measurements2021
- Online Event Detection in Synchrophasor Data with Graph Signal Processing2020
- Tackling Issues Related to PMU Deployment in the Grid using a Novel Algorithm2020
- IEEE/IEC International Standard - Measuring relays and protection equipment - Part 118-1: Synchrophasor for power systems - Measurements2018
- Impact of Causality on Performance of Phasor Measurement Unit Algorithms2018
- Wide-area monitoring and control at Hydro-Quebec: past, present and future2006
- Sequential Quadratic ProgrammingActa Numerica, 1995
- A derivation of an analytic expression for the tracking index for the alpha-beta-gamma filterIEEE Transactions on Aerospace and Electronic Systems, 1993