Adjusting the Parameters of Metal Oxide Gapless Surge Arresters’ Equivalent Circuits Using the Harmony Search Method
Open Access
Abstract
The appropriate circuit modeling of metal oxide gapless surge arresters is critical for insulation coordination studies. Metal oxide arresters present a dynamic behavior for fast front surges; namely, their residual voltage is dependent on the peak value, as well as the duration of the injected impulse current, and should therefore not only be represented by non-linear elements. The aim of the current work is to adjust the parameters of the most frequently used surge arresters’ circuit models by considering the magnitude of the residual voltage, as well as the dissipated energy for given pulses. In this aim, the harmony search method is implemented to adjust parameter values of the arrester equivalent circuit models. This functions by minimizing a defined objective function that compares the simulation outcomes with the manufacturer’s data and the results obtained from previous methodologies.Keywords
This publication has 18 references indexed in Scilit:
- Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in ParallelInternational Journal of Power and Energy Research, 2017
- Analysis of power quality improvement in smart grids2017
- Analysis of electromagnetic disturbances for grid-connected PV plants2015
- Improvement of estimation of surge arrester parameters by using Modified Particle Swarm OptimizationEnergy, 2011
- Estimation of the parameters of metal oxide gapless surge arrester equivalent circuit models using genetic algorithmElectric Power Systems Research, 2011
- Application of Powell’s optimization method to surge arrester circuit models’ parametersEnergy, 2010
- Parameters' optimisation for surge arrester circuit modelsIET Science, Measurement & Technology, 2010
- Assessment of surge arrester failure rate and application studies in Hellenic high voltage transmission linesElectric Power Systems Research, 2010
- Parameter identification of ZnO surge arrester models based on genetic algorithmsElectric Power Systems Research, 2008
- A simplified model for zinc oxide surge arrestersIEEE Transactions on Power Delivery, 1999