The object of this study is a class B fire, which is extinguished with sprayed water. The subject of the study is the characteristics of class B fires when they are extinguished with sprayed water. Diffusion burning of a flammable liquid is considered as such a fire, and its extinguishing is carried out by cooling the flame. Heat and oxygen balance equations are used to build a mathematical model describing the fire extinguishing process. The components of the heat balance equation are the power of heat during heat release due to the chemical reaction of liquid combustion and the power of heat dissipated to the environment. The second component takes into account heat removal due to radiation, convection, and evaporation. The component of removed heat due to evaporation takes into account the Sreznevsky constant. The mathematical model that describes the process of extinguishing a class B fire is built in the class of models belonging to differential equations with constant coefficients. Analytical expressions were obtained for these static and dynamic coefficients, which include thermophysical, kinematic, and geometric parameters of the flame and fire extinguishing agent. To determine these characteristics, the constructed mathematical fire model was transformed using the integral Laplace transform. The dynamic characteristics of the fire were obtained in the time domain – the transient function of the fire, and in the frequency domain – the amplitude-frequency and phase-frequency characteristics of the fire. It is shown that the parameters of these dynamic characteristics should be determined experimentally. Experimental methods for determining parameters of dynamic fire characteristics have been devised. The presence of dynamic characteristics of class B fire makes it possible to spread the proven methods of the theory of control systems to design effective fire extinguishing systemsKeywords
This publication has 16 references indexed in Scilit:
- The investigation of the water mist suppression pool fire process's flame expansion characteristicsJournal of Loss Prevention in the Process Industries, 2022
- Study on the effect of mist flux on water mist fire extinguishingFire Safety Journal, 2022
- CFD-based study and analysis on the effectiveness of water mist in interacting pool fire suppressionProcess Safety and Environmental Protection, 2021
- Performance by Various Water Mist Nozzles in Extinguishing Liquid Pool FiresFire Technology, 2021
- Experimental investigation on spray characteristics of twin-fluid nozzle for water mist and its heptane pool fire extinguishing performanceProcess Safety and Environmental Protection, 2021
- Theoretical and numerical study on influence of wind on mass loss rates of heptane pool fires at different scalesFire Safety Journal, 2021
- Characterization of solid-cone simplex mist nozzlesFire Safety Journal, 2020
- Gasoline fire extinguishing by 0.7 MPa water mist with multicomponent additives driven by CO2Process Safety and Environmental Protection, 2019
- An infrared scattering by evaporating droplets at the initial stage of a pool fire suppression by water spraysInfrared Physics & Technology, 2018
- Preliminary study on fire protection of window glass by water mist curtainInternational Journal of Thermal Sciences, 2018