Modulation and SSR tests performed on the BPA 500 kV thyristor controlled series capacitor unit at Slatt substation
Authors:
- J.F. HauerJHJ.F. Hauer
- W.A. MittelstadtWMW.A. Mittelstadt
- R.J. PiwkoRPR.J. Piwko
- B.L. DamskyBDB.L. Damsky
- J.D. EdenJEJ.D. Eden
- 1 May 1996
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 11 (2) , 801-806
Abstract
Field experience is reported for a thyristor controlled series capacitor (TCSC) recently commissioned at BPA's Slatt substation. Subsynchronous resonance tests show that TCSC interactions with shaft dynamics of PGE's Boardman steam generator are well understood and are effectively avoided by normal TCSC valve firing logic. Modulation tests, performed with the Boardman plant offline, show that the TCSC can be a powerful and responsive actuator for swing damping. Security considerations did not permit lightly damped operation of the controlled plant. Close analysis indicates that the TCSC damping contribution, though small, was measurable. The best estimate is that damping for the McNary mode is 7.33% and 8.55%, for the TCSC damper loop open and closed respectively. TCSC testing and monitoring is facilitated by an advanced interactive measurement network representing BPA's approach to the information requirements of major control systems.Keywords
This publication has 8 references indexed in Scilit:
- Estimating damping effectiveness of BPA's thyristor controlled series capacitor by applying time and frequency domain methods to measured responseIEEE Transactions on Power Systems, 1996
- A study of TCSC optimal damping control parameters for different operating conditionsIEEE Transactions on Power Systems, 1995
- Thyristor controlled series compensation prototype installation at the Slatt 500 kV substationIEEE Transactions on Power Delivery, 1993
- Analysis of second harmonic instability for the Chateauguay HVDC/SVC schemeIEEE Transactions on Power Delivery, 1992
- The future of transmission - Switching to siliconIEEE Power Engineering Review, 1989
- Robust damping controls for large power systemsIEEE Control Systems Magazine, 1989
- The Intermountain Power Project commissioning-subsynchronous torsional interaction testsIEEE Transactions on Power Delivery, 1988
- How HVDC schemes can excite torsional oscillations in turbo-alternator shaftsIEE Proceedings C Generation, Transmission and Distribution, 1986