Sparse Estimation of Faults by Compressed Sensing With Structural Constraints
- 6 April 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 33 (6) , 5935-5944
Abstract
This paper addresses the challenge of fault location in large power networks using a limited number of sensors. It was recently shown that power system faults may be modeled by sparse vectors, and hence, can be located efficiently using sparse recovery techniques. In this paper, we extend this approach and propose a sparse recovery algorithm that exploits both the sparsity constraints and additional structural constraints imposed by the faults physical models. To this end, faults are represented by sparse vectors that are subjected to nonconvex constraints. These constraints are shown to provide additional information that is exploited to reduce the number of measurements and to improve the location accuracy. The algorithm searches directly over these physical faults, and therefore, operates over a small solution space. Simulations on the IEEE 118 bus test-case network show that 4 to 20 sensors are sufficient to recover faults with adequate accuracy. With 20 PMU sensors, more than 99% of single-fault events and 84%-95% of two-fault events are located, depending on fault types and SNR.Keywords
Funding Information
- Grand Technion Energy Program
This publication has 36 references indexed in Scilit:
- A Novel Method for Fault Location of Transmission Lines by Wide-Area Voltage Measurements Considering Measurement ErrorsIEEE Transactions on Smart Grid, 2014
- Fault Location in Distribution Networks by Compressive SensingIEEE Transactions on Power Delivery, 2014
- A Sparse Representation Approach to Online Estimation of Power System Distribution FactorsIEEE Transactions on Power Systems, 2014
- A Straightforward Method for Wide-Area Fault Location on Transmission NetworksIEEE Transactions on Power Delivery, 2014
- Distributed Power-Line Outage Detection Based on Wide Area Measurement SystemSensors, 2014
- Application of synchronised phasor measurements to wide‐area fault diagnosis and locationIET Generation, Transmission & Distribution, 2014
- An Efficient PMU-Based Fault-Location Technique for Multiterminal Transmission LinesIEEE Transactions on Power Delivery, 2014
- Distribution Grid State Estimation from Compressed MeasurementsIEEE Transactions on Smart Grid, 2014
- Efficient Identification Method for Power Line Outages in the Smart Power GridIEEE Transactions on Power Systems, 2014
- A Universal Fault Location Technique for N-Terminal $({N}\geqq 3)$ Transmission LinesIEEE Transactions on Power Delivery, 2008