Application of Digital Image Processing to Detect Short-Circuit Turns in Power Transformers Using Frequency Response Analysis
Authors:
- 27 July 2016
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Informatics
- Vol. 12 (6) , 2062-2073
Abstract
Although a frequency response analysis (FRA) technique has been extensively used to detect mechanical deformation within power transformers, interpretation of FRA signature still needs a high level of expertise to identify and quantify faults as there is no FRA interpretation code widely accepted yet. All commercial frequency response analyzers can measure the magnitude and phase angle of the impedance, admittance, or transfer function of each phase in a wide frequency range; however, only magnitude is currently used for fault identification and quantification. This paper presents a novel approach for FRA signature interpretation by incorporating the FRA magnitude and phase plots into one polar plot that captures more features of the measured signal than the magnitude plot. Digital image processing-based techniques are employed to automate the fault identification and quantification process. To investigate the impact of transformer rating and size on the proposed technique, two transformers of different ratings and physical geometrical dimensions are simulated using 3-D finite-element analysis to emulate transformer real operation. Short-circuit of various fault levels is simulated at various locations within the high-voltage and low-voltage windings of the two transformer models and the obtained FRA polar plot signature for each case study is analyzed and compared with the healthy signature. Also, practical measurement is conducted to validate the simulation results. Results show that fault level along with fault location can be easily identified using the proposed polar plot signature along with the developed digital image processing technique.Keywords
This publication has 18 references indexed in Scilit:
- Improved power transformer winding fault detection using FRA diagnostics – part 1: axial displacement simulationIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Application of FRA polar plot technique to diagnose internal faults in power transformers2014
- Lifetime estimation and monitoring of power transformer considering annual load factorsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Detection of Failures Within Transformers by FRA Using Multiresolution DecompositionIEEE Transactions on Power Delivery, 2014
- Dynamic Deformation Analysis of Power Transformer Windings in Short-Circuit Fault by FEMIEEE Transactions on Applied Superconductivity, 2013
- Understanding power transformer frequency response analysis signaturesIEEE Electrical Insulation Magazine, 2013
- A new approach to identify power transformer criticality and asset management decision based on dissolved gas-in-oil analysisIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Modeling Power Transformers to Support the Interpretation of Frequency-Response AnalysisIEEE Transactions on Power Delivery, 2011
- Finite-Element Analysis of Short-Circuit Electromagnetic Force in Power TransformerIEEE Transactions on Industry Applications, 2011
- Winding movement in power transformers: a comparison of FRA measurement connection methodsIEEE Transactions on Dielectrics and Electrical Insulation, 2006