On the effects of HV/MV stations on global grounding systems
- 1 September 2016
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Abstract
The METERGLOB project has faced the issue of the identification of Global Grounding Systems. One of the main point of the problem is to define if an interconnection of single grounding systems gives place to a Global Grounding System in any condition and for every kind of ground fault. This paper focuses the attention on what happens in the case of single line to ground fault inside a HV/MV station whose ground electrode is connected to the cable' shields of the MV lines outgoing the station and supplying the secondary substations of a given area.Keywords
This publication has 6 references indexed in Scilit:
- The identification of global earthing systems: A review and comparison of methodologies2016
- Single grounding system intrinsically safe and global grounding system safe as set2016
- The Global Grounding System: Definitions and guidelines2015
- Influence of LV neutral grounding on global Earthing Systems2015
- Globality levels of grounding systems2014
- Globalization of electrical safety codes and standards2002