A New Method of Fault Direction Identification for Different Types of Renewable Energy Source Integrations
- 12 October 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (4) , 2932-2941
Abstract
The characteristics of the short circuit current of renewable energy sources are quite different from those of traditional generators. When applied to tie lines and collector lines of renewable energy sources, the traditional directional elements may not operate correctly. A new method of fault direction identification suitable for inverter power sources and doubly fed power sources based on the fault features of renewable energy sources is proposed. The fault type is judged by sequence voltage. The fault direction is identified by comparing the amplitude between the sequence currents and the phase angle between the sequence voltage and the sequence current, without distinguishing whether the crowbar of the DFIG is triggered. The results of digital simulations and experiments show that this method is not affected by the types of renewable energy sources connected to the power grid and can correctly judge the fault direction in different fault types, which has good engineering application value.Keywords
Funding Information
- National Key R&D Program of China (2016YFB0900600)
This publication has 12 references indexed in Scilit:
- Control Strategy for Three-Phase Grid-Connected PV Inverters Enabling Current Limitation Under Unbalanced FaultsIEEE Transactions on Industrial Electronics, 2017
- Fault Characteristics Analysis and Line Protection Design Within a Large-Scale Photovoltaic Power PlantIEEE Transactions on Smart Grid, 2017
- A novel directional relay applicable to power system with wind farms2016
- Adaptability Analysis of Directional Relays in Power Systems with Wind Farms2016
- Equivalent circuit of DFIG with crowbar protection for relay protection analysis2016
- Influence on transmission line relay protection under DFIG-based wind farm intergration2015
- Study on the fault current transient features of the PV inverter2015
- Three-Phase Fault Direction Identification for Distribution Systems With DFIG-Based Wind DGIEEE Transactions on Sustainable Energy, 2014
- Directional relays without voltage sensors for distribution grids: Optimal boundaries for fault direction estimation2013