Performance Problem of Current Differential Protection of Lines Emanating from Photovoltaic Power Plants
Open Access
- 14 February 2020
- journal article
- research article
- Published by MDPI AG in Sustainability
- Vol. 12 (4) , 1436
Abstract
The amplitude and phase angle of the fault current in photovoltaic power plants (PVPPs) are significantly influenced by the control system of the grid-connected inverters, unlike in a conventional synchronous source. Hence, PVPPs may adversely affect the performance of the current differential protection designed for synchronous sources-based power grids. In order to study the performance problem of current differential protection on AC transmission lines, an analytical expression of the fault current in the PVPPs was deduced, and the fault current characteristic was extensively analyzed. Based on this analysis, the ratio of differential current over restraint current was initially derived in this study; this ratio is observed to be affected by the control system parameters, power grid system parameters, fault resistance, and fault types. Moreover, the dynamic characteristics of this ratio can be clearly observed based on a three-dimensional diagram. Furthermore, the operating performance of the current differential protection was analyzed under different influencing factors. The mathematical analysis presents that the amplitude ratio of the fault current on both sides of the line is larger than nine and that current differential protection will operate reliably in any case. Meanwhile, the theoretical analysis and simulation results show that the current phase angle difference may become an obtuse angle in case of an ungrounded fault, which will cause inaccurate operation of the current differential protection. The results of this study will provide guidance for the engineering application of current differential protection in case the PVPPs are connected to a power grid.Keywords
Funding Information
- National Natural Science Foundation of China (51707193)
This publication has 27 references indexed in Scilit:
- Principle and Implementation of Current Differential Protection in Distribution Networks With High Penetration of DGsIEEE Transactions on Power Delivery, 2016
- Fault Transient Analysis and Protection Performance Evaluation within a Large-scale PV Power PlantMATEC Web of Conferences, 2016
- Control of Active and Reactive Power Ripple to Mitigate Unbalanced Grid VoltagesIEEE Transactions on Industry Applications, 2015
- Smart inverter operation in distribution networks with high penetration of photovoltaic systemsJournal of Modern Power Systems and Clean Energy, 2015
- Grid-Connected Photovoltaic Systems: An Overview of Recent Research and Emerging PV Converter TechnologyIEEE Industrial Electronics Magazine, 2015
- Distance Protection of Lines Emanating From Full-Scale Converter-Interfaced Renewable Energy Power Plants—Part II: Solution Description and EvaluationIEEE Transactions on Power Delivery, 2014
- Distance Protection of Lines Emanating From Full-Scale Converter-Interfaced Renewable Energy Power Plants—Part I: Problem StatementIEEE Transactions on Power Delivery, 2014
- Differential relaying scheme for tapped transmission line connecting UPFC and wind farmInternational Journal of Electrical Power & Energy Systems, 2014
- A Unified Dynamic Model and Control for the Voltage-Sourced Converter Under Unbalanced Grid ConditionsIEEE Transactions on Power Delivery, 2006
- Dual current control scheme for PWM converter under unbalanced input voltage conditionsIEEE Transactions on Industrial Electronics, 1999