A Transient Voltage-Based DC Fault Line Protection Scheme for MMC-Based DC Grid Embedding DC Breakers
- 8 October 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 34 (1) , 334-345
Abstract
Fast and reliable DC fault detection is one of the main challenges for modular multilevel converter (MMC) based DC grid with DC circuit breakers (DCCBs). This paper extracts the high-frequency components in transient voltages by wavelet transform and proposes a fault identification method based on the difference of square of transient voltages to identify the faulted lines for DC grids using overhead lines. Meanwhile, a faulted pole discrimination method based on the difference between the change of positive and negative pole voltages is presented. A line protection scheme including detection activation, fault identification, faulted pole discrimination and post-fault re-closing is designed. Using only the local measurements, the scheme can realize the protection of the whole line without communication and has the capability of fault resistance endurance and anti-disturbance. The proposed method is tested with a four-terminal MMC based DC grid in PSCAD/EMTDC. The selection methods of threshold values are presented and the impact of DCCB operation on the reliability of DC fault protection is analysed. Simulation results verify the fast detection and reliability of the designed DC line protection scheme.Keywords
Funding Information
- National Natural Science Foundation of China (U1766211)
This publication has 26 references indexed in Scilit:
- Fast Frequency Response From Offshore Multiterminal VSC–HVDC SchemesIEEE Transactions on Power Delivery, 2016
- Fault detection in HVDC system using Short Time Fourier Transform2016
- Transient-Voltage-Based Protection Scheme for DC Line Faults in the Multiterminal VSC-HVDC SystemIEEE Transactions on Power Delivery, 2016
- DC Fault Detection and Location in Meshed Multiterminal HVDC Systems Based on DC Reactor Voltage Change RateIEEE Transactions on Power Delivery, 2016
- Analysis of the Performance of MMC Under Fault Conditions in HVDC-Based Offshore Wind FarmsIEEE Transactions on Power Delivery, 2015
- Implementation and Application of Practical Traveling-Wave-Based Directional Protection in UHV Transmission LinesIEEE Transactions on Power Delivery, 2015
- A novel whole-line quick-action protection principle for HVDC transmission lines using one-end voltageInternational Journal of Electrical Power & Energy Systems, 2015
- Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC BreakersIEEE Transactions on Power Delivery, 2014
- Development of a Novel Protection Device for Bipolar HVDC Transmission LinesIEEE Transactions on Power Delivery, 2014
- A sensitive and high-speed traveling wave protection scheme for HVDC transmission lineInternational Transactions on Electrical Energy Systems, 2013