Improved Fault Location Through Analysis of System Parameters During Autoreclose Operations on Transmission Lines
- 9 October 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 29 (6) , 2430-2438
Abstract
This paper describes a novel single-ended impedance-based fault-location method for transmission lines, which is based upon the analysis of voltage and current during discrete system states that arise during the operation of single- and three-phase autoreclose schemes. A fault-location estimation algorithm, using the data measured during various system states and is capable of locating the fault types involving one fault resistance (i.e., single-line-to-ground fault or line-to-line fault), is developed and presented. The proposed fault-location technique is shown to have high accuracy; results are presented and compared with the well-established Takagi method and the performance of the algorithm is analyzed and discussed. The proposed technique can reduce or negate limitations associated with conventional single-ended methods and can also estimate other factors associated with the fault (e.g., fault resistance and remote source impedance). In addition, it is a potentially economic solution, since it is relatively straightforward to implement on a standard protection relay hardware platform. The proposed method is demonstrated using Electromagnetic Transients Program/Alternate Transients Program simulation models for a variety of different cases. This paper concludes with an overview of ongoing and future work that has the intention of moving the work forward toward implementation within commercially available relay hardware.Keywords
This publication has 13 references indexed in Scilit:
- Fast auto-reclose function for 765 KV lines in the proximity of resonant line voltages2010
- Accurate Noniterative Fault Location Algorithm Utilizing Two-End Unsynchronized MeasurementsIEEE Transactions on Power Delivery, 2009
- Impedance-Based Fault Location Experience2006
- Fault Location on a Transmission Line Using Synchronized Voltage MeasurementsIEEE Transactions on Power Delivery, 2004
- Investigation of practical problems for digital fault location algorithms based on EMTP simulation2003
- Adaptive measuring algorithm suppressing a decaying DC component for digital protective relaysElectric Power Systems Research, 2001
- Fault location using the high frequency travelling waves measured at a single location on a transmission line2001
- Travelling wave fault locator experience on Eskom's transmission network2001
- A new accurate fault locating algorithm for series compensated lines1999
- An Accurate Fault Locator With Compensation For Apparent Reactance In The Fault Resistance Resulting From Remore-End InfeedIEEE Transactions on Power Apparatus and Systems, 1985