Abstract
Under conditions of systemic instability and growing military threats to critical infrastructure facilities, the development of a methodology for adaptive risk management of cascading failures in water treatment systems is of particular importance for ensuring their survivability and protecting thermal power equipment. Traditional reliability assessment methods may be insufficient for accounting for the cascading nature of transient processes in technological installations, where a local failure may propagate to adjacent system components and lead to deterioration in the quality of the heat-transfer medium. To ensure the survivability of water treatment systems and protect thermal power equipment under conditions of military and technogenic instability, a methodology for adaptive risk management of cascading failures has been developed based on reliability theory and Kolmogorov differential equations. Analysis of the developed mathematical approach made it possible to establish that: 1) a mathematical model of system-state dynamics was developed based on Kolmogorov differential equations, in which the transition rates between states depend on the adaptive control vector, thereby enabling the occurrence of a cascading failure to be formalized as a probabilistic transition between system states; 2) a method was proposed for determining the adaptive control parameters of an electrocoagulation unit by minimizing deviations of water-treatment quality indicators from their specified values while simultaneously accounting for specific energy consumption; 3) an approach was developed for the quantitative assessment of an adaptive resilience index characterizing the preservation of system functionality throughout the disturbance period–from the onset of failure to the restoration of the specified treatment parameters; 4) a mathematical approach was proposed for determining instantaneous and integral adaptive risk as the expected value of system-related technological losses, thereby enabling the identification of potentially vulnerable elements of the technological scheme; 5) it was substantiated that adaptive management of electrocoagulation units may contribute to the localization of cascading failures, the maintenance of stable treated-water quality, and a reduction in the risk of damage to thermal power equipment caused by disturbances in the water-chemical regime. Quantitative assessment of the effectiveness of the proposed approach requires further mathematical modelling and experimental verification.