Thermal Performance of an Air-Cooled Data Center With Raised-Floor and Non-Raised-Floor Configurations
- 30 September 2013
- journal article
- research article
- Published by Taylor & Francis in Heat Transfer Engineering
- Vol. 35 (4) , 384-397
Abstract
In this paper, the thermal performances of an air-cooled data center with raised-floor and non-raised-floor configurations are compared with respect to the room and ceiling return strategies. The thermal performance of the data center is evaluated in terms of supply heat index, rack cooling index, total irreversible loss, and the number of racks with at least one server exceeding the maximum recommended and allowable inlet air temperature according to American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) thermal guidelines. The numerical simulations are conducted providing an insight into the flow and temperature distributions, and thus giving a better understanding of the cooling issues. It is found that using a ceiling return strategy for the return of hot exhaust air to the computer room air conditioning units gives a better thermal performance of the data center, for both raised- and non-raised-floor strategy, as compared to the room return. The findings are then extended to a geometrically complex operational data center to improve its cooling effectiveness. The paper also highlights the drawback of using supply heat index alone as a performance metric.Keywords
This publication has 10 references indexed in Scilit:
- A Comparison of Parametric and Multivariable Optimization Techniques in a Raised-Floor Data CenterJournal of Electronic Packaging, 2013
- Cooling solutions in an operational data centre: A case studyApplied Thermal Engineering, 2011
- Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centersEnergy and Buildings, 2011
- Improving Data Center EfficiencyEnergy Engineering, 2010
- Convective Transport Processes in Data CentersNumerical Heat Transfer, Part A: Applications, 2006
- Energy Efficiency In Computer Data CentersEnergy Engineering, 2006
- Cluster of High-Powered Racks Within a Raised-Floor Computer Data Center: Effect of Perforated Tile Flow Distribution on Rack Inlet Air TemperaturesJournal of Electronic Packaging, 2004
- On the performance and use of dense serversIBM Journal of Research and Development, 2003
- The IEEE standards on reliability program and reliability prediction methods for electronic equipmentMicroelectronics Reliability, 2002
- A methodology for the design of perforated tiles in raised floor data centers using computational flow analysisIEEE Transactions on Components and Packaging Technologies, 2001