Failure Analysis of Direct Liquid Cooling System in Data Centers
- 9 May 2018
- journal article
- research article
- Published by ASME International in Journal of Electronic Packaging
- Vol. 140 (2)
Abstract
In this paper, the impact of direct liquid cooling (DLC) system failure on the information technology (IT) equipment is studied experimentally. The main factors that are anticipated to affect the IT equipment response during failure are the central processing unit (CPU) utilization, coolant set point temperature (SPT), and the server type. These factors are varied experimentally and the IT equipment response is studied in terms of chip temperature and power, CPU utilization, and total server power. It was found that failure of this cooling system is hazardous and can lead to data center shutdown in less than a minute. Additionally, the CPU frequency throttling mechanism was found to be vital to understand the change in chip temperature, power, and utilization. Other mechanisms associated with high temperatures were also observed such as the leakage power and the fans' speed change. Finally, possible remedies are proposed to reduce the probability and the consequences of the cooling system failure.Keywords
Funding Information
- National Science Foundation (1307228)
- National Science Foundation (IIP-1134867)
This publication has 13 references indexed in Scilit:
- Pressure drop analysis of direct liquid cooled (DLC) rack2017
- Improving Data Center Energy Efficiency With Advanced Thermal ManagementIEEE Transactions on Components, Packaging and Manufacturing Technology, 2017
- Combining cooling technology and facility design to improve HPC data center energy efficiency2016
- A Holistic Evaluation of Data Center Water Cooling Total Cost of OwnershipJournal of Electronic Packaging, 2016
- A Brief Overview of Recent Developments in Thermal Management in Data CentersJournal of Electronic Packaging, 2015
- Benefit of Cold Aisle Containment During Cooling Failure2013
- Extreme energy efficiency using water cooled servers inside a chiller-less data center2012
- Impact of operating conditions on a chiller-less data center test facility with liquid cooled servers2012
- Energy Efficiency Analyses and Comparison of Air and Water Cooled High Performance Servers2009
- The evolution of water cooling for IBM large server systems: Back to the future2008