Effect Mechanism of Ambient Air Parameters on the Thermal Performance for Cooling Towers
- 16 November 2023
- journal article
- research article
- Published by Wiley in Journal of Thermal Science and Engineering Applications
- Vol. 16 (1) , 1-25
Abstract
As the volume of natural draft wet cooling towers (NDWCTs) continues to increase, the influence of ambient air on the thermal performance of the NDWCT is not clear. Therefore, the main parameters such as gas–water ratio, circulating water temperature difference, and heat transfer in each zone were calculated, and the temperature field and humidity field were also investigated. The results showed that the ambient temperature had the greatest influence on the cooling capacity of the NDWCT and the increase of ambient temperature led the circulating water temperature difference decreases the most, which was 7.63 °C (74.15%). The increase of relative humidity and atmospheric pressure led to an increase in convective heat transfer and the decrease in evaporative mass transfer, while both the convective heat transfer and evaporative mass transfer reduced with the decreasing temperature. This study establishes a theoretical foundation for optimizing of the thermal performance and energy-saving design of NDWCTs.Keywords
Funding Information
- Natural Science Foundation of Hebei Province (E2022502052)
- Fundamental Research Funds for the Central Universities (2022MS081)
This publication has 18 references indexed in Scilit:
- An exploratory research on performance improvement of super-large natural draft wet cooling tower based on the reconstructed dry-wet hybrid rain zone, part 2: Crosswind effectsInternational Journal of Heat and Mass Transfer, 2020
- A Review of Rotating Stall in Vaneless Diffuser of Centrifugal CompressorJournal of Thermal Science, 2020
- Study of Rotating Stall in a Centrifugal Compressor with Wide Vaneless DiffuserJournal of Thermal Science, 2020
- Field test study on water droplet diameter distribution in the rain zone of a natural draft wet cooling towerApplied Thermal Engineering, 2019
- An exploratory research on performance improvement of super-large natural draft wet cooling tower based on the reconstructed dry-wet hybrid rain zoneInternational Journal of Heat and Mass Transfer, 2019
- Field test study on thermal and ventilation performance for natural draft wet cooling tower after structural improvementApplied Thermal Engineering, 2019
- Numerical simulation of thermal performance for super large-scale wet cooling tower equipped with an axial fanInternational Journal of Heat and Mass Transfer, 2019
- Study on static and dynamic characteristics of an axial fan with abnormal blade under rotating stall conditionsEnergy, 2019
- Novel method for improving the cooling performance of natural draft wet cooling towersApplied Thermal Engineering, 2019
- Experimental research of the cross walls effect on the thermal performance of wet cooling towers under crosswind conditionsApplied Thermal Engineering, 2011