DC electrical breakdown dependence on the radial position of specimens within HVDc XLPE cable insulation
Authors:
- 29 June 2017
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 24 (3) , 1476-1484
Abstract
Because of temperature gradients and inhomogeneous cooling rates after extrusion, the performances of HVDC XLPE cable insulation at radial position are not uniformly distributed. DC breakdown strength measurements of HVDC XLPE cable insulation specimens in inner insulation (near conductor shield), middle insulation and outer insulation (near insulation shield) have been carried out and show that DC breakdown strength of specimens in middle insulation is relatively lower than that of in inner and outer insulation at 30, 50 and 70 °C. At 90 °C, there is no significant difference of DC breakdown strength of specimens at radial position. Thus the micro performances of XLPE specimens at different radial position have been studied by FTIR, DSC, SEM and XRD. FTIR measurements show that cross-linked by-products (benzyl alcohol and acetophenone) content in middle insulation is higher; DSC measurements shows that crystallinity of specimens in middle insulation is slightly higher; SEM measurements show that the grains of specimens in middle insulation are unevenly distributed and their sizes have obvious difference; the results of XRD measurements show a higher content of by-products, a higher crystallinity and a larger crystalline interplanar spacing (a larger grain size) of specimens in middle insulation, which are consistent with FTIR, DSC and SEM analysis. Therefore, cross-linked by-products, crystallinity and crystal morphology together make DC breakdown strength of specimens in middle insulation lower.Keywords
This publication has 17 references indexed in Scilit:
- HVDC, the next generation of transmission highlights with focus on extruded cable systems2008
- Electric characterization of films peeled from the insulation of extruded HVDC cables2005
- Effect of acetophenone on electric conduction in LDPE film2002
- Influence of post-manufacturing residual mechanical stress and crosslinking by-products on dielectric strength of HV extruded cablesIEEE Transactions on Dielectrics and Electrical Insulation, 2002
- Characterizing HV XLPE cables by electrical, chemical and microstructural measurements on cable peeling: effects of surface roughness, thermal treatment and peeling location2000
- The influence of defects on the short-term breakdown characteristics and long-term dc performance of LDPE insulationIEEE Transactions on Dielectrics and Electrical Insulation, 2000
- Dielectric Properties and Morphology in PolyethyleneIEEE Transactions on Electrical Insulation, 1980
- Relation between Electrical Impulse Breakdown Strength and Rate of Drawing in PolyethyleneJapanese Journal of Applied Physics, 1979
- Effect of Elongation on Dielectric Breakdown Strength in PolyethyleneJapanese Journal of Applied Physics, 1975
- The electric strength of paraffins and some high polymersJournal of the Institution of Electrical Engineers - Part I: General, 1946