Calibration of Phasor Measurement Unit at NIST
Authors:
- 11 February 2013
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 62 (6) , 1417-1422
Abstract
This paper describes the basic operating principles of Phasor Measurement Units (PMUs) and their time requirements to estimate absolute phase angles. A National Institute of Standards and Technology (NIST) PMU calibration system that tests PMU performance necessary to meet the IEEE synchrophasor standard requirements is discussed. The calibration of voltage, current, and time measurements for the NIST PMU test system is described. The total vector error of the NIST PMU test system is estimated to be 0.05%. A comparison between the NIST PMU test system and a prototype commercial PMU calibrator was performed to assure traceability of relevant electrical measurements and time measurement.Keywords
This publication has 8 references indexed in Scilit:
- Calibration of phasor measurement unit at NIST2012
- Dynamic characterization of PMUs using step signals2009
- Reference Values for Dynamic Calibration of PMUs2008
- Dynamic Phasor Measurement Unit Test System2007 IEEE Power Engineering Society General Meeting, 2007
- Intercomparison of Calibration Systems for AC Shunts Up to Audio FrequenciesIEEE Transactions on Instrumentation and Measurement, 2005
- A four terminal current shunt with calculable AC response2004
- Evaluation of uncertainty in AC voltage measurement using a digital voltmeter and Swerlein's algorithm2003
- Wide-Band Two-Stage Current Transformers of High AccuracyIEEE Transactions on Instrumentation and Measurement, 1972