Design and Application of a Low-Ratio High-Accuracy Split-Core Core-Balance Current Transformer
Authors:
- 26 July 2010
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 46 (5) , 1856-1865
Abstract
This paper describes the design and application of a split-core current transformer (CT) of large dimensions, specifically designed for mounting in a 13.8-kV switchgear cubical on the phase bus bars. Although split-core CTs of high current ratio are available, the authors believe that the core-balance CT described in this paper is unique, as no similar CT was readily available in the U.S./European market. Thus, there is no equivalent installation in the industry of the specifications described in this paper. The CT discussed in this paper was specifically designed to meet the requirements of dimensions and accuracy for sensitive ground fault and directional ground fault relaying.Keywords
This publication has 3 references indexed in Scilit:
- CT Saturation Calculations: Are They Applicable in the Modern World?—Part I: The QuestionIEEE Transactions on Industry Applications, 2007
- Ground Fault Protection for Bus-Connected Generators in an Interconnected 13.8-kV SystemIEEE Transactions on Industry Applications, 2007
- Relay performance considerations with low-ratio CTs and high-fault currentsIEEE Transactions on Industry Applications, 1995