Partial discharge localization in transformers using UHF sensors
Authors:
- 1 June 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 23340975,p. 64-68
Abstract
The location of the partial discharge (PD) source inside a transformer can be determined by using the time differences between signals that are captured by an array of three UHF sensors. However, other unwanted signals are also picked up by the sensors and may result in a false PD location. This paper discusses the application of multivariate denoising to the PD signals. Three methods are compared to determine the time difference between the received signals and locate the PD source. With the first peak method, the time difference is calculated by taking the first peak of the signal as the arrival instant. In the second method, the arrival time is determined from the knee point of the cumulative energy curve. For the third method, the time difference is determined by applying the similarity function to the plot of the cumulative energy of the PD signals. The last method is fully automated. However, experimental results show the first peak method tends to be the most accurate.Keywords
This publication has 9 references indexed in Scilit:
- Study of Time Delay of UHF Signal Arrival in Location Partial Discharge2008
- Sensor response characteristics for UHF location of PD sources2008
- Experimental investigation of positional accuracy for UHF partial discharge location2008
- Wavelet-based partial discharge image denoisingIET Generation, Transmission & Distribution, 2007
- Partial discharge location in power transformers using wideband RF detectionIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Multivariate denoising using wavelets and principal component analysisComputational Statistics & Data Analysis, 2006
- Partial discharge monitoring of power transformers using UHF sensors. Part I: sensors and signal interpretationIEEE Electrical Insulation Magazine, 2005
- Denoising UHF signal for PD detection in transformers based on wavelet technique2004
- Power transformer monitoring using UHF sensors: site trials2002