Experimental study on a cross-flow energy recovered indirect evaporative cooling (ERIEC)-assisted liquid desiccant dehumidifier (LDD) with improved spraying nozzle and surface wetness
- 30 March 2021
- journal article
- research article
- Published by Taylor & Francis in Science and Technology for the Built Environment
- Vol. 27 (7) , 903-916
Abstract
The film wetted area is a significant factor affecting the heat and mass transfer of liquid desiccant. In this article, a mathematical model with wetness coefficient of cross-flow energy recovered indirect evaporative cooling (ERIEC)-assisted liquid desiccant dehumidifier (LDD) based on a finite-element method was developed to predict the effect of wetness coefficient on the plate heat exchanger (PHE) effectiveness and dehumidification efficiency, taking into account the thermal resistance and incomplete wetting of liquid film. In addition, an experimental system of a cross-flow ERIEC-assisted LDD was established to validate the model; the validation of the model demonstrated good agreement with the experimental data to within 10%. With this model, increasing the wetness coefficient from 0.1 to 1, the PHE effectiveness gradually increased from 3.7% to 39.1% and the dehumidification efficiency increased gradually from 3.5% to 35.2%. This meant that the nonwetting or partial wetting of liquid film hindered the dehumidification performance. Therefore, a novel TiO2 super-hydrophilic coating was applied to raise the wetness coefficient and improve the dehumidification performance. Within the experimental range, spraying a super-hydrophilic coating (1% nanosized TiO2 solution) in the primary channel of the dehumidifier could increase the PHE effectiveness and dehumidification efficiency by 2.5–5% and 5–30%, respectively.Keywords
Funding Information
- National Natural Science Foundation of China (51678385)
This publication has 25 references indexed in Scilit:
- An adaptive full-range decoupled ventilation strategy for buildings with spaces requiring strict humidity control and its applications in different climatic conditionsSustainable Cities and Society, 2020
- Development of a novel quasi-3D model to investigate the performance of a falling film dehumidifier with CFD technologyInternational Journal of Heat and Mass Transfer, 2019
- Numerical modeling of fluid flow and coupled heat and mass transfer in a counter-cross-flow parallel-plate liquid-to-air membrane energy exchangerInternational Journal of Heat and Mass Transfer, 2015
- Model validation and case study on internally cooled/heated dehumidifier/regenerator of liquid desiccant systemsInternational Journal of Thermal Sciences, 2009
- An analytical model for heat and mass transfer processes in internally cooled or heated liquid desiccant–air contact unitsInternational Journal of Heat and Mass Transfer, 2007
- Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regeneratorEnergy Conversion and Management, 2007
- Modeling of heat and mass transfer in parallel plate liquid-desiccant dehumidifiersSolar Energy, 2006
- Numerical simulation and theoretical analysis of heat and mass transfer in a cross flow liquid desiccant air dehumidifier packed with honeycomb paperEnergy Conversion and Management, 2004
- Modelling and performance analysis of a cross-flow type plate heat exchanger for dehumidification/coolingSolar Energy, 2001
- Experimental studies on the dehumidifier and regenerator of a liquid desiccant cooling systemApplied Thermal Engineering, 2000