Optimising thermal performance in data centre server racks via a parametric layout configuration study
Open Access
- 25 June 2026
- journal article
- Published by Springer Nature in Scientific Reports
- Vol. 16 (1)
Abstract
The rapid expansion of data centres has intensified the demand for low-threshold thermal optimisation strategies that avoid the high costs and operational disruptions associated with conventional infrastructure retrofits. This study focuses exclusively on in-rack server layout adjustments, specifically server power combination, arrangement methods, and air supply velocity. A dedicated experimental platform was constructed to represent a standard server rack environment, and physical single-factor and orthogonal experiments were conducted to evaluate cooling efficiency. Results indicate that: (1) Heat accumulates primarily at the rack top, producing pronounced temperature stratification. (2) The relative impact of the examined parameters on thermal performance ranks as follows: air supply velocity > power combination > arrangement method. (3) An optimal configuration—400 W × 10 servers positioned in the lower rack with an air supply velocity of 4 m/s—effectively alleviates heat imbalance and suppresses hot-spots. Compared with a non-optimised baseline, this configuration yielded measurable improvements in airflow utilisation and thermal uniformity. This work demonstrates that strategic in-rack layout adjustments alone can markedly enhance cooling performance without additional capital investment or infrastructure modifications, offering actionable guidance for data centre operators seeking practical, low-effort optimisation measures.Keywords
Funding Information
- the Guizhou University Laboratory Open Project (No. SYSKF2025-026)
- Undergraduate Innovation and Entrepreneurship Training Program Project (No.gzusc2025127)
- Guizhou Provincial Basic Research Program (Qiankehe Foundation MS[2026]181)
- Guizhou Province Postgraduate Research Fund Project (No.2024YJSKYJJ114)
This publication has 40 references indexed in Scilit:
- Experimental evaluation of thermal characteristics of wall mounted radiant cooled environment with ceiling fanSādhanā, 2024
- Optimization air-conditioning system and thermal management of data center via fan-wall free cooling technologyApplied Thermal Engineering, 2023
- Experimental and numerical investigation on thermal performance of data center via fan-wall free cooling technologyApplied Thermal Engineering, 2023
- An experimental and numerical investigation of novel solution for energy management enhancement in data centers using underfloor plenum porous obstructionsApplied Energy, 2021
- Design and validation of an airflow management system in data center with tilted server placementApplied Thermal Engineering, 2020
- A review on airflow management in data centersApplied Energy, 2019
- Recent advancements on thermal management and evaluation for data centersApplied Thermal Engineering, 2018
- An experimental and theoretical investigation of the extent of bypass air within data centres employing aisle containment, and its impact on power consumptionApplied Energy, 2017
- Quantified risk assessment in railway system design and operationQuality and Reliability Engineering International, 1995
- Describing the uncertainties in experimental resultsExperimental Thermal and Fluid Science, 1988