Abstract
Single phase-to-ground (SPG) faults in distribution active networks can cause serious hazards, such as fire accidents, electrical shocks, and power outages. Power converters can be connected to a neutral point of distribution networks to suppress fault current and voltage until the fault arc disappears. However, typical current- or voltage-based arc suppression methods alone, using the controls of proportional-integral (PIC), proportional-lagging (PLC), backstepping (BSC), or sliding mode (SMC), etc., cannot adapt to uncertain and variable fault resistances, causing a long transient response process and residual fault current and voltage, resulting in the fault arc not being extinguished quickly and reliably. This paper proposes a nonlinear adaptive controller (NAC) design-based fault current and voltage fusion suppression method. The proposed method integrates both fault current and voltage suppression methods, and covers variable and unknown fault resistances. It can follow Lyapunov's asymptotic stability. Thus, the proposed method can better suppress fault current and voltage, and adapt to variable fault resistances. Simulation study and experimental validation demonstrate that not only are the fault current and voltage simultaneously suppressed without a long transient response time under different fault resistances, but also the residual fault current and voltage are smaller, compared with the typical methods.