Exposure Risk to Medical Staff in a Nasopharyngeal Swab Sampling Cabin under Four Different Ventilation Strategies
Open Access
Abstract
Medical staff working in a nasopharyngeal swab sampling cabin are exposed to a higher exposure risk of COVID-19. In this study, computational fluid dynamics (CFD) are used to evaluate the exposure risk to medical staff in a nasopharyngeal swab sampling cabin of Chinese customs under four different ventilation strategies, i.e., multiple supply fans ventilation (MSFV), multiple exhaust fans ventilation (MEFV), single exhaust fan and outer windows closed ventilation (SEFV), and single exhaust fan and outer windows opened ventilation (SEFV-W). The impact of physical partitions on exposure risk is also discussed. The results show that MSFV performed best in reducing exposure risk. No significant difference was found between MEFV and SEFV. SEFV-W performed better than SEFV with a ventilation rate of 10–50 L/(s∙Person), while it performed worse with a ventilation rate of 50–90 L/(s∙Person). The exposure risk to medical staff did not decrease linearly with the increase in the ventilation flow rate under the four ventilation strategies. For MSFV, the installation of partitions is conducive to the reduction in the exposure risk. This study is expected to provide some guidance for ventilation designs in sampling cabins.Keywords
Funding Information
- National Natural Science Foundation of China (41977370)
- Special fund of Beijing Key Laboratory of Indoor Air Quality Evaluation and Control (BZ0344KF20-0)
This publication has 45 references indexed in Scilit:
- Measuring the exhaled breath of a manikin and human subjectsIndoor Air, 2014
- Human convective boundary layer and its interaction with room ventilation flowIndoor Air, 2014
- Exhaled Air Dispersion during Coughing with and without Wearing a Surgical or N95 MaskPLOS ONE, 2012
- Risk assessment of airborne infectious diseases in aircraft cabinsIndoor Air, 2012
- Observing and quantifying airflows in the infection control of aerosol- and airborne-transmitted diseases: an overview of approachesJournal of Hospital Infection, 2011
- Risk of cross-infection in a hospital ward with downward ventilationBuilding and Environment, 2010
- Dispersion of exhalation pollutants in a two-bed hospital ward with a downward ventilation systemBuilding and Environment, 2008
- Dispersion of exhaled droplet nuclei in a two-bed hospital ward with three different ventilation systemsIndoor Air, 2006
- Measurement and prediction of indoor air flow in a model roomEnergy and Buildings, 2003
- AIRBORNE SPREAD OF MEASLES IN A SUBURBAN ELEMENTARY SCHOOLAmerican Journal of Epidemiology, 1978