Effect of Magnetic Field on Different Opening Processes of Multi-Break Vacuum Gaps
Open Access
- 21 January 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 9, 17222-17228
Abstract
Vacuum gap saturation of single break can be solved by multiple breaks in series. In different breaking processes, the unbalanced energy and charges injected into the breaks lead to unbalanced voltage distribution. The purpose of this paper was to compare the voltage distribution under the regulation of magnetic field in different opening process. The magnetic fields with 3 ms width were applied at the point 3 ms before current through zero. Comparing with no axial magnetic field, the voltage distribution unbalances deceased both in synchronous and asynchronous opening processes. Under the condition that the arcing time of high-voltage break remained at 6.6 ms and the magnitude of axial magnetic fields was 60 mT, voltage distributions of high-voltage break were approximately proportional to the arcing times of the low-voltage break from 3.4 ms to 6.6 ms. It demonstrated that axial magnetic fields could effectively improve the voltage distribution of multi-break vacuum circuit breakers in synchronous and asynchronous opening processes.Keywords
Funding Information
- National Natural Science Foundation of China (51777025)
- Fundamental Research Funds for the Central Universities (DUT19ZD219)
This publication has 16 references indexed in Scilit:
- Experimental Investigation Into the Synergy of Vacuum Circuit Breaker With Double-BreakIEEE Transactions on Plasma Science, 2015
- Study on Static and Dynamic Voltage Distribution Characteristics and Voltage Sharing Design of a 126-kV Modular Triple-Break Vacuum Circuit BreakerIEEE Transactions on Plasma Science, 2015
- Relationship Between the Voltage Distribution Ratio and the Post Arc Current in Double-Break Vacuum Circuit BreakersIEEE Transactions on Plasma Science, 2009
- Interruption characteristics of double-break vacuum circuit breakersIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Influence of grading capacitors on the breaking performance of a 24-kV vacuum breaker series designIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- Vacuum interrupter model based on breaking testsIEEE Transactions on Plasma Science, 1999
- Characteristics of a vacuum switching contact based on bipolar axial magnetic fieldIEEE Transactions on Plasma Science, 1999
- Influence of grading capacitors on the breaking capacity of two vacuum interrupters in seriesIEEE Transactions on Dielectrics and Electrical Insulation, 1999
- Simulation of reignition processes of vacuum circuit breakers in seriesIEEE Transactions on Dielectrics and Electrical Insulation, 1997
- Effect of an axial magnetic field upon the development of the vacuum arc between opening electric currents (currents read contacts)IEEE Transactions on Components, Hybrids, and Manufacturing Technology, 1993