Analysis of Cause of Fire and Explosion in Internal Floating Roof Tank: Focusing on Fire and Explosion Accidents at the OO Oil Pipeline Corporation
Authors:
- Chae-Chil KooCKChae-Chil Koo
- Jae-Wook ChoiJCJae-Wook Choi
Open Access
- 30 April 2020
- journal article
- research article
- Published by Korea Institute of Fire Science and Engineering in Fire Science and Engineering
- Vol. 34 (2) , 86-93
Abstract
This study aims to maintain the safety of an outdoor storage tank through the fundamental case analysis of explosion and fire accidents in the storage tank. We consider an accident caused by the explosion of fire inside the tank, as a result of the gradual spreading of the residual fire generated by wind lamps flying off a workplace in the storage tank yard. To determine the cause of the accident, atmospheric diffusion conditions were derived through CCTV image analysis, and the wind direction was analyzed using computational fluid dynamics. Additionally, the amount of oil vapor inside the tank when the floating roof was at the lowest position, and the behavior of the vapor inside the tank when the floating roof was at the highest position were investigated. If the cause of the explosion in the storage tank is identified and the level of the storage tank is maintained below the internal floating roof, dangerous liquid fills the storage tank, and the vapor in the space may stagnate on the internal floating roof. We intend to improve the operation procedure such that the level of the storage tank is not under the Pontoon support, as well as provide measures to prevent flames from entering the storage tank by installing a flame arrester in the open vent of the tank.Keywords
Funding Information
- Pukyong National University
This publication has 6 references indexed in Scilit:
- Study of Fire and Explosion Prevention of an Internal Floating Roof TankFire Science and Engineering, 2019
- The Study on the Countermeasure Plans about Leakage, Explosion and Fire Accidents of Atmospheric Storage TankFire Science and Engineering, 2016
- Accident scenarios triggered by lightning strike on atmospheric storage tanksReliability Engineering & System Safety, 2014
- Explosion of fixed roof atmospheric storage tanks, part 1: Background and review of case historiesProcess Safety Progress, 2011
- Storage tank fire accidentsProcess Safety Progress, 2011
- A study of storage tank accidentsJournal of Loss Prevention in the Process Industries, 2006