On-Line Monitoring of Maximum Temperature and Loss Distribution of a Medium Frequency Transformer Using Artificial Neural Networks
- 25 August 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 38 (12) , 15818-15828
Abstract
Losses and maximum temperature are important indicators of the health status of the medium-frequency magnetic components. Both the losses and the maximum temperature are very difficult to obtain/estimate due to the high complexity, change of losses in the core with respect to the average temperature, or the variation of the losses of the windings derived from the construction of the litz wire and the high-frequency effects. This article proposes the use of a real-time estimator, based on artificial neural networks trained from finite element method simulations capable of predicting with an error less than 2% in all cases both the maximum internal temperatures and the losses of a medium frequency transformer, with forced convection, which implies a very complex thermal behavior.Keywords
Funding Information
- OPEMRES (TED2021-130610B-C21)
- CRESIPS-PE (PID2021-125628OB-C22)
- Ministerio de Ciencia e Innovación, Spain
This publication has 31 references indexed in Scilit:
- Thermal modeling and experimental verification of an air cooled medium frequency transformer2017
- A review of transformer aging and control strategies2017
- Using power state estimation to calculate hotspot temperature of distribution transformers2015
- Iron Losses in a Medium-Frequency Transformer Operated in a High-Power DC–DC ConverterIEEE Transactions on Magnetics, 2014
- Fiber Bragg grating sensor for detecting ageing transformer oil2012
- Closed Form Solution for Minimum Conduction Loss Modulation of DAB ConvertersIEEE Transactions on Power Electronics, 2012
- Thermal Aging of Distribution Transformers According to IEEE and IEC Standards2007 IEEE Power Engineering Society General Meeting, 2007
- Diagnosis of transformer insulation condition using recovery voltage measurements2005
- Derating of distribution transformers for non-sinusoidal load currents using finite element method2004
- Optimal choice for number of strands in a litz-wire transformer windingIEEE Transactions on Power Electronics, 1999