State-Estimation-Based Determination of Harmonic Current Contributions of Iron and Steel Plants Supplied from PCC
- 25 January 2016
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 52 (3) , 2654-2663
Abstract
In this paper, a state-estimation-based method is proposed to determine harmonic current contributions of iron and steel (I&S) plants supplied from a point of common coupling (PCC). Due to highly nonlinear nature of the I&S plant operation, accurate estimation of harmonic contributions of the individual plants is essential. In the proposed method, the nonlinear characteristics of the plants and the utility are modeled as harmonic current sources and the harmonic current contributions of loads are decoupled from the upstream effects on the basis of the sample-by-sample time-synchronized field measurements of load currents and voltage signals. Being a field-measurement-based method, it is necessary to mitigate the measurement errors of conventional voltage transformers (CVTs) at harmonic frequencies. Gross error of voltage transformers is reduced through calibration, while weighted least squares (WLS) state estimation is used to reduce the Gaussian error of the current transformer and calibrated voltage transformer measurements. Using the estimated harmonic voltages and currents, harmonic contributions of all plants are determined by employing the Norton equivalent circuits of the plants together with the superposition theorem. The results have shown that the proposed method can be used as a successful estimation tool to determine the harmonic current contributions of all I&S plants supplied from the PCC. The proposed method eliminates the need for the usage of resistive-capacitive voltage transformers (RCVTs) for accurate harmonic voltage measurements, which are expensive and cumbersome, while reducing the Gaussian measurement error of conventional voltage and current transformers at the same time; hence, it provides accurate harmonic contributions of the electric arc furnace (EAF) plants.Keywords
Funding Information
- IEEE Industry Applications Society Annual Meeting
- IEEE Industry Applications Society
This publication has 9 references indexed in Scilit:
- LAV Based Robust State Estimation for Systems Measured by PMUsIEEE Transactions on Smart Grid, 2014
- Identification of Harmonic Current Contributions of Iron and Steel Plants Based on Time-Synchronized Field Measurements—Part II: Inside PlantsIEEE Transactions on Industry Applications, 2014
- Nationwide real-time monitoring system for electrical quantities and power quality of the electricity transmission systemIET Generation, Transmission & Distribution, 2011
- On harmonic state estimation and the evaluation of harmonic power contributions from sources2010
- Power System State Estimation2004
- Identification of harmonic sources of power systems using state estimationIEE Proceedings - Generation, Transmission and Distribution, 1999
- Reliable Bad Data Processing for Real-Time State EstimationIEEE Transactions on Power Apparatus and Systems, 1983
- Power System Static-State Estimation, Part I: Exact ModelIEEE Transactions on Power Apparatus and Systems, 1970