Impact of Load Frequency Dependence on the NDZ and Performance of the SFS Islanding Detection Method
Authors:
- 6 October 2009
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 58 (1) , 139-146
Abstract
Sandia frequency shift (SFS) falls under the active islanding detection methods that rely on frequency drift to detect an islanding condition for inverter-based distributed generation. Active islanding detection methods are commonly tested on constant RLC loads where the load's active power is directly proportional to the square of voltage and is independent on the system frequency. Since the SFS method relies primarily on frequency to detect islanding, the load's active power frequency dependence could have an impact on its performance and the nondetection zone (NDZ). In this paper, the impact of the load's active power frequency dependence on the performance of the SFS method, during an islanding condition, is analyzed. A NDZ model that takes into account the load's frequency dependence parameter is derived mathematically and validated through digital simulation. The results show that the load's frequency dependence has a significant impact on the NDZ of the SFS method and thus is an important factor to consider when designing and testing this method.Keywords
This publication has 23 references indexed in Scilit:
- Performance of the OVP/UVP and OFP/UFP Method With Voltage and Frequency Dependent LoadsIEEE Transactions on Power Delivery, 2009
- A Hybrid Islanding Detection Technique Using Average Rate of Voltage Change and Real Power ShiftIEEE Transactions on Power Delivery, 2009
- Sandia Frequency-Shift Parameter Selection to Eliminate Nondetection ZonesIEEE Transactions on Power Delivery, 2008
- Impact of DG Interface Controls on the Sandia Frequency Shift Antiislanding MethodIEEE Transactions on Energy Conversion, 2007
- A Hybrid Islanding Detection Technique Using Voltage Unbalance and Frequency Set PointIEEE Transactions on Power Systems, 2007
- Experimental Investigation on Non Detection Zones of Active Frequency Drift Method for Anti-islanding2007
- Power-Electronic Systems for the Grid Integration of Renewable Energy Sources: A SurveyIEEE Transactions on Industrial Electronics, 2006
- Performance Assessment of Active Frequency Drifting Islanding Detection MethodsIEEE Transactions on Energy Conversion, 2006
- FPGA-based islanding detection for grid connected inverter2005
- Determining the relative effectiveness of islanding detection methods using phase criteria and nondetection zonesIEEE Transactions on Energy Conversion, 2000