An Experimental Study of Short-Circuit Current Making Operation of Air Medium-Voltage Load Break Switches
- 24 February 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (6) , 4646-4656
Abstract
Replacing SF6, the most potent greenhouse gas, with an alternative is a challenge that medium-voltage load break switch (MV-LBS) has faced. Air is a possible alternative, but there are some challenges regarding low dielectric strength leading to high arcing time and dissipated energy. Therefore, understanding the switching operations in air MV-LBS is crucial to design efficient compact switchgear. This work focuses on making operations in air MV-LBS. A synthetic test circuit and a model switch are designed based on the standards to simulate making operations under fault conditions similar to a real test. The test condition is set to achieve high pre-strike arcing time and energy. The results show that the most destructive impact of the making short-circuit current occurs in the first half-cycle of the load current when the pre-strike arc is formed. With an average short-circuit current with a peak of 22 kA and a breakdown voltage of 20 kV, the switch failed to re-open due to the arcing contacts welding after four successive making operations without main contacts and seven successive operations with main contacts. It has been shown that the total arcing contact mass loss occurs mainly during the pre-arcing time.Keywords
Funding Information
- Norges Forskningsråd (269361)
This publication has 21 references indexed in Scilit:
- Evaluation method of contact erosion for high voltage SF 6 circuit breakers using dynamic contact resistance measurementElectric Power Systems Research, 2018
- Visualization and mechanisms of splashing erosion of electrodes in a DC air arcJournal of Physics D: Applied Physics, 2017
- Power Switching Components2017
- Online Condition Assessment of Interruption Chamber of Gas Circuit Breakers Using Arc Voltage MeasurementIEEE Transactions on Power Delivery, 2016
- Empirical Relationships Between Air-Load Break Switch Parameters and Interrupting PerformanceIEEE Transactions on Power Delivery, 2015
- Interruption in Air for Different Medium-Voltage Switching DutiesIEEE Transactions on Power Delivery, 2014
- Investigation on Erosion of Cu/W Contacts in High-Voltage Circuit BreakersIEEE Transactions on Components and Packaging Technologies, 2006
- Erosion and resistance characteristics of AgW and AgC contactsIEEE Transactions on Components and Packaging Technologies, 1999
- Heat transfer and cold cathode erosion in electric arc heatersIEEE Transactions on Plasma Science, 1997
- Total voltage drops in electrode fall regions of , argon and air arcs in current range from 10 to 20 000 AJournal of Physics D: Applied Physics, 1996