Abstract
This letter proposes a novel method to extract singlemode feedback signals using a modal eigenvalue realignment (MER) based approach. The single-mode feedback signals those contain information pertinent to the concerned modes are selected, while states with minimal participation are disregarded. These signals are utilized as supplementary inputs to highvoltage direct current (HVDC) tie-line converter and exciters of synchronous generators (SGs) aiming to enhance the damping of inter-area modes (IAMs) of oscillation. The proposed method is thoroughly evaluated and validated using a 25-machine, 105-bus Eastern Regional (ER) truncated power system of India, and further verified through real-time hardware-in-the-loop (HIL) simulation.

This publication has 10 references indexed in Scilit: