Impact of Distributed Generation Integration on Protection Devices: A Case Study in the CIGRE European Medium Voltage Network
Open Access
- 23 September 2024
- conference paper
- Published by MDPI AG in Engineering Proceedings
- Vol. 77 (1) , 9
Abstract
This study examines the impact of Inverter-Based Distributed Generators (IIDGs) on short-circuit currents detected by the main relay at the head of a radial feeder. It highlights how changes in fault currents induced by these inverter technologies can significantly affect the effectiveness and reliability of network protection systems. Key variables, such as the level of IIDGs penetration and the relative location of faults with respect to the relay, have been identified as influential factors. The significance of these findings lies in their contribution to a deeper understanding of how inverter fault responses and the integration of IIDGs alter fault currents. To mitigate the adverse effects associated with the insertion of IIDGs, a fault-detection and tripping strategy based on the inverse-time overcurrent curve is proposed. The suggested strategies not only improve fault detection accuracy but also ensure an appropriate response to variations in network conditions.Keywords
Funding Information
- German Academic Exchange Service (57519668)
This publication has 11 references indexed in Scilit:
- Evaluation of Grid-Following Inverter Control Models for Fault Response and their Impact on Protection Devices2024
- Demand response model: A cooperative-competitive multi-agent reinforcement learning approachEngineering Applications of Artificial Intelligence, 2024
- Adaptive overcurrent protection scheme coordination in presence of distributed generation using radial basis neural networkProtection and Control of Modern Power Systems, 2023
- Impact of Inverter-Based Distributed Generation Integration on Current Seen by Overcurrent Relay: CIGGRE European MV Network Case2023
- An approach to disparage the blindness of backup protection in grid connected renewable energy sources system by inducing artificial fault currentInternational Journal of Electrical Power & Energy Systems, 2023
- Impact of distributed generation on the protection systems of distribution networks: analysis and remedies – review paperIET Generation, Transmission & Distribution, 2020
- Protection challenges under bulk penetration of renewable energy resources in power systems: A reviewCSEE Journal of Power and Energy Systems, 2017
- Progress on Protection Strategies to Mitigate the Impact of Renewable Distributed Generation on Distribution SystemsEnergies, 2017
- Morphological Fault Detector for Adaptive Overcurrent Protection in Distribution Networks With Increasing Photovoltaic PenetrationIEEE Transactions on Sustainable Energy, 2017
- Short circuit analysis and adaptive zonal protection of distribution system with distributed generators2015