Novel Black-Box Arc Model Validated by High-Voltage Circuit Breaker Testing
- 18 October 2017
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 33 (4) , 1835-1844
Abstract
In this paper, we present a new black-box arc model that was validated using tests with short-line fault interruption of high-voltage circuit breakers. This new arc model shows superior performance compared with four types of existing black-box arc models. Black-box arc models are widely used to simulate current and voltage waveforms during the interruption process. Applied together with arc parameters, they determine arc conductance and interruption behavior. In this study, the arc parameters of each arc model are derived from an optimization approach in a defined time interval, to minimize the difference between the measured and simulated arc voltages. The black-box arc models with optimized arc parameters are applied to a simplified circuit for short-line fault simulation, and the model accuracy of the interruption prediction and waveform fitting are quantitatively scored.Keywords
This publication has 3 references indexed in Scilit:
- Evaluation of high-voltage circuit breaker performance with a new validated arc modelIEE Proceedings - Generation, Transmission and Distribution, 2000
- Application of a new arc model for the evaluation of short-circuit breaking testsIEEE Transactions on Power Delivery, 1993
- Beiträge zur Theorie des statischen und des dynamischen LichtbogensElectrical Engineering, 1943