RSRene Peter Paul Smeets

Rene Peter Paul Smeets

*This is an algorithmically generated author record based on publicly available information.

Rene Peter Paul Smeets has a total of 26 co-authors. Here are the top co-authors by number of shared publications:


Latest Publications

  • Open Access

    Innovative T&D Switching Equipment and Development of its Testing Technology

    by René P.P. Smeets, Arman Derviškadić, Adriaan B. Hofstee, Roy M. Nijman, Nadew A. Belda, Benjamin Baum

    A short overview of the developments in the overall transmission and distribution industry in South East Europe is presented in this contribution. Furthermore, as the present journal focuses on breaking and switching in HV and MV switchgears, several technology innovations in T&D switchgear have been identified, at global level. In almost all cases, the ongoing energy transition is the main driver of these innovations. In this contribution, based on test-experience and overview of the industry, innovations are grouped by drivers, with each of them having its impact on testing technology. These drivers are the following: 1. Increase of ratings: the ongoing trend of co-existence of micro-, local- and super-grids. The consequences for testing of switchgear for UHV and very large current are highlighted: 2. Offshore transmission: compactness and reliability are requirements stretched to the limit for this application. Very long cables for AC and HVDC power transmission, even in a multi-terminal topology will have impact on switchgear. 3. Health safety and environment: here, the major switchgear related discussion is on SF 6 replacement and reduction of electrical losses. Various issues related to SF 6 replacement will be highlighted. In addition, a recent project intended to quantify the hazard of aluminium bus bars in power stations affected by long duration fault arcs is described. 4. HVDC and power electronics: circuit breakers are going to be installed in multi-terminal HVDC grids. Testing of HVDC breakers, regarding the complete interruption current process is described. 5. Digitalization: switchgear is going to be communicating with the IEC 61850 communication protocol. This will impact testing for which laboratories need to prepare. The introduction of smaller micro-electronics (sensors, IED) closer to primary HV components and its high-frequency transients need careful consideration regarding operation, endurance, and lifetime. 6. Resilience and fault mitigation: Resilience against severe weather conditions, vandalism and cyber-attacks calls for resistant equipment and robust mobile equ ipment/substations that can 6be deployed very rapidly still having an extreme degree of readiness and availability. 7. Quality assurance of products in the face of a pandemic and a lockdown requires adequate methods of a remote digital access to test, and factory sites for type testing and inspection.


  • Thermal FEM Analysis of Surge Arresters During HVdc Current Interruption Validated by Experiments

    by Siyuan Liu, Marjan Popov, Nadew Adisu Belda, René Peter Paul Smeets, Zhiyuan Liu

    This paper deals with the development of an accurate finite-element model of an arrester to investigate the electrothermal and mechanical stress during dc current interruption. The comprehensive analysis performed on a ZnO surge arrester is supported by experiments during high-voltage dc circuit breaker current interruption. The performed experimental analysis comprises three sequential 26 kV/10 kA direct current interruption tests carried out within a period of one hour. The dynamic temperature and current distribution of the surge arrester columns during current interruption are measured. The finite-element simulation results are in good agreement with the test results. The influence of the surge arrester temperature on the current distribution among the surge arrester columns is analyzed. The impact of the surge arrester temperature on ZnO electrical characteristics and mechanical stress inside the surge arrester are also investigated. The surge arrester finite-element model can be used with full success for parameter optimization of the surge arresters to prevent possible failures when dc circuit breakers performed multiple interruptions in short period of time.


  • Open Access

    High‐voltage direct current fault current interruption: A technology review

    by Rene P. P. Smeets, Nadew A. Belda

    This review paper describes fault current interruption principles and various high‐voltage direct currrent (HVDC) circuit breaker technologies. First, fundamentals of HVDC fault current interruption and a generic set of requirements of HVDC circuit breakers are presented. The critical parameters during fault current interruption are assessed using a simplified mathematical model. Then, the state‐of‐the‐art of HVDC circuit breaker technologies and their application in actual HVDC multi‐terminal projects is highlighted. Several sub‐components of HVDC circuit breakers are standard components used in a non‐standard application and, hence, have to face non‐standard stresses. All of today's HVDC circuit breaker technologies consist of mechanical switching devices and metal‐oxide surge arresters, which are used in an unconventional way. A critical analysis of these stresses compared to the stresses in a conventional application is provided. Recommendations on testing supported with examples of actual full‐power ‘complete’ demonstration of HVDC circuit breakers up to 350 kV/20 kA are discussed. Finally, the actual status of standardisation activities is presented.


  • Experimental Investigation of Electrical Stresses on the Main Components of HVDC Circuit Breakers

    by Nadew Adisu Belda, René Peter Paul Smeets, Roy Maarten Nijman

    Recently a number HVdc circuit breakers (CBs) based on various dc current interruption principles have been developed and a few are put in operation. However, due to a lack of practical experience, no clearly defined requirements that the HVdc CBs should satisfy exist. To define and refine justified test requirements, a thorough understanding of the interactions between the internal components of the HVdc CB and the stresses on these components is necessary. In this paper, an experimental dc CB based on the active current injection is setup in a high-power laboratory to investigate the performances of the main components; namely, the vacuum interrupter (VI) and the metal oxide surge arrester (MOSA). The performances of three different designs VIs are investigated and it is found out that each of the VIs behave completely different. Moreover, the performance of a MOSA, designed for HVdc CB application, is also investigated by applying energy per volume ranging between 70-220 J/cm3 at temperature as high as 250 °C. In order to find out the performance limit of the MOSA for this application, successive high-energy tests are performed until electro-mechanical failures occur in the MO varistors. Various failure modes such as fracturing, and puncture are observed.


  • High-Frequency Current Interruption of Vacuum Interrupters in an Experimental DC Circuit Breaker

    by Nadew A. Belda, Rene P. P. Smeets, Roy M. Nijman, Michalis Poikilidis, Cornelis A. Plet

    Recently, several manufacturers have proposed and developed prototypes of high-voltage direct current (HVDC) circuit breakers (CBs) based on various dc current interruption principles. However, due to a lack of operational experience with this type of equipment, no clearly defined requirements that these new developments should satisfy exist. To define and refine justified test requirements, a thorough understanding of the interactions between the internal components of the HVDC CBs and the stresses on these components is necessary. For this purpose, an experimental dc CB based on the active current injection technique is setup in a high-power laboratory. The contribution of this paper focuses on the performance of vacuum interrupters (VIs) for dc CB application. The performances of three different VIs, designed for ac application, are investigated. About 200 tests, under different test conditions, have been conducted in which up to 850 current zero crossings (CZCs) are created. The test results are analyzed and presented in detail along with statistical information obtained from the analysis of the measured parameters. The test results serve to identify the critical stages of current interruption process that need to be demonstrated during typical current interruption tests of HVDC CBs. It is found that the three types of VIs behave very differently; the rate-of-change of current near CZCs is not the only key parameter; and successful current interruptions can still be achieved after re-ignitions and re-strikes.


  • Full-Power Test of HVDC Circuit-Breakers With AC Short-Circuit Generators Operated at Low Power Frequency

    by Nadew Adisu Belda, Cornelis Arie Plet, Rene Peter Paul Smeets

    This paper provides a pragmatic solution to the challenge of testing fault current interruption of high-voltage direct current (HVDC) circuit breakers (CBs). The critical parameters in the design of a test circuit capable of supplying the necessary stresses: current, energy, and voltage (both during and after interruption) are discussed. In addition, a practical implementation of a test circuit based on ac short-circuit generators operated at low power frequency, which is capable of testing the current interruption performance of the proposed technologies of HVDC CBs, is discussed. Tests validating the proposed method and circuit have been conducted on a prototype of an HVDC CB and the test results are presented. Since the performance of some technologies of HVDC CBs can depend on the magnitude of the interrupted current, four test duties are defined and demonstrated in the paper. Moreover, testing of HVDC CBs using ac short-circuit generators poses new challenges, such as the application of dielectric dc stress after current interruption and the protection of both the test-object as well as the test-circuit components when the HVDC CB fails to interrupt. Methods to overcome these challenges are developed and practically demonstrated in a test laboratory. Finally, taking into account the available resources of the author's test laboratory, the capability to test multiple series-connected modules of different technologies of HVDC CBs is verified and example cases are demonstrated. Six short-circuit generators (13 500 MVA @ 50 Hz) and up to ten step-up transformers (up to 550 kV) were actually used.


  • Novel Black-Box Arc Model Validated by High-Voltage Circuit Breaker Testing

    by Toshiya Ohtaka, Viktor Kertesz, Rene Peter Paul Smeets

    In this paper, we present a new black-box arc model that was validated using tests with short-line fault interruption of high-voltage circuit breakers. This new arc model shows superior performance compared with four types of existing black-box arc models. Black-box arc models are widely used to simulate current and voltage waveforms during the interruption process. Applied together with arc parameters, they determine arc conductance and interruption behavior. In this study, the arc parameters of each arc model are derived from an optimization approach in a defined time interval, to minimize the difference between the measured and simulated arc voltages. The black-box arc models with optimized arc parameters are applied to a simplified circuit for short-line fault simulation, and the model accuracy of the interruption prediction and waveform fitting are quantitatively scored.


  • Top Cited Papers

    Analysis of Faults in Multiterminal HVDC Grid for Definition of Test Requirements of HVDC Circuit Breakers

    by Nadew Adisu Belda, Cornelis Arie Plet, Rene Peter Paul Smeets

    This paper provides a detailed analysis of the temporal development of fault currents in a multiterminal high-voltage direct-current (MT-HVDC) grid composed of a bipolar converter configuration. The sequence of events following the occurrence of a pole-to-ground fault is identified, divided into three distinct periods; namely, submodule capacitor discharge, arm current decay, and ac in-feed periods. The critical parameters that have a significant impact on the fault current in each period are discussed. The impacts of various parameters of the HVDC grid such as the size of the current limiting reactor, ac grid strength, as well as the location of the fault within the grid are studied through PSCAD/EMTDC simulation. Then, a fault current interruption process using models of various HVDC circuit breaker technologies and the resulting stresses are studied. Both serve as important inputs to define test procedures. It is found that the HVDC circuit breakers are subjected to not only dc current and voltage stresses but also energy stress. These stresses are translated into test requirements.


  • Design of test-circuits for HVDC circuit breakers

    by R.P.P. Smeets, A. Yanushkevich, N.A. Belda, R. Scharrenberg

    DC circuit breakers are essential components in the protection of multi-terminal and meshed DC grids. So far, no practical application of HVDC circuit breakers is known and intense research is being carried out regarding various concepts, practical realization and ultimately testing of such devices. In the present contribution, several breaker concepts, based on the hybrid method of DC fault current interruption, described in (patent-) literature, are modelled in order to investigate their interaction with a DC grid. For this purpose, the CIGRE B4 test-system, a combination of DC and AC grids, consisting of multiple in-feeds and having lines and cables, is modelled. The impact of a fault on the breaker is considered. Since industrial concepts of hybrid HVDC breakers are modelled including their key elements, the electrical stresses on various parts of the breakers are analyzed in detail. These stresses are used as a guide to design high-power test circuits that can be used to test DC switchgear under realistic conditions. Two classes of DC test circuits are considered and investigated based on high-power test circuits, supplied by AC generators: · One class can produce pseudo-DC currents of short duration that can be adequate to test DC equipment (including switchgear) under normal and fault conditions. Three basic circuits will be demonstrated and compared. · Another class is a set of basic test-circuits having capability of creating similar stresses on HVDC circuit breakers as in service. Four basic circuits are investigated and compared to an ideal DC circuit: discharge of a charged high-current reactor, discharge of a charged high-voltage capacitor bank and high-power high-voltage AC circuits of 16.7 and 50 Hz. Comparison of each of these circuits shows that low frequency AC circuits are possible candidates to represent the interaction of HVDC circuit breaker with a DC circuit adequately; regarding fault current rise, interruption performance, counter voltage creation and energy management.