Performance Assessment and Improvement of Two‐Phase Immersion Cooling for Multi‐Chip Module
- 26 May 2025
- journal article
- Published by Wiley in Asia-Pacific Journal of Chemical Engineering
- Vol. 20 (4)
Abstract
Thermal management of chips is a key bottleneck to power densification. Two‐phase immersion methods provide a potential alternative to realize the goal of thermal management on chips. In this paper, a numerical model of a multi‐chip module is established to evaluate the thermal performance of two‐phase immersion cooling based on the CFD method. The effects of coolant type, inlet velocity, and subcooling are investigated. The results indicate that the coolant type, inlet velocity, and subcooling significantly affect the temperature of the multi‐chip module. Compared with FC‐72, the chip temperature dropped considerably by using Novec7100, which has higher latent heat. When the inlet subcooling remains constant, the chip temperature gradually decreases as the coolant flow rate increases. The chip temperature remains virtually stable when the inlet velocity exceeds 0.8 m/s. For this model, the optimal subcooling should be around 30°C. The baffle can effectively improve the overall temperature uniformity of the multi‐chip module. The addition of the baffle can reduce the temperature uniformity coefficient of the chip by up to 63.08%. After further optimization, the temperature uniformity is increased by 35.89%.Keywords
Funding Information
- Natural Science Foundation of Gansu Province (25JRRA922)
This publication has 28 references indexed in Scilit:
- Experimental study on the immersion liquid cooling performance of high-power data center serversEnergy, 2024
- Enhancing the cooling efficiency of the air cooling system for electric vehicle battery modules through liquid spray integrationJournal of Energy Storage, 2023
- Heat transfer characteristics and influencing factors of immersion coupled direct cooling for battery thermal managementJournal of Energy Storage, 2023
- Experimental studies of liquid immersion cooling for 18650 lithium-ion battery under different discharging conditionsCase Studies in Thermal Engineering, 2022
- Simulation study on cooling effect of two-phase liquid-immersion cabinet in data centerApplied Thermal Engineering, 2022
- System-level experimental investigations of the direct immersion cooling data center units with thermodynamic and thermoeconomic assessmentsEnergy, 2021
- A novel thermal management scheme for 3D-IC chips with multi-cores and high power densityApplied Thermal Engineering, 2020
- Performance optimization of cascaded and non-cascaded thermoelectric devices for cooling computer chipsEnergy Conversion and Management, 2019
- A continuum method for modeling surface tensionJournal of Computational Physics, 1992
- Thermodynamic Analysis of Resorption Heat Pump Cycle Using Water-Multicomponent Salt Mixture1990