An Innovative Device for the Hot Water Circuit in Hospitals to Save Energy Without Compromising the Safety and Quality of Water: Preliminary Results
Authors:
- Sara VincentiSVSara Vincenti
- Mario Cesare NurchisMNMario Cesare Nurchis
- Federica BonintiFBFederica Boninti
- Martina SapienzaMSMartina Sapienza
- Matteo RaponiMRMatteo Raponi
- Fabio PattavinaFPFabio Pattavina
- Carlo PesaroCPCarlo Pesaro
- Carlo D’alonzoCDCarlo D’alonzo
- Gianfranco DamianiGianfranco Damiani
- Patrizia LaurentiPLPatrizia Laurenti
Open Access
Abstract
Legionella colonization of water systems represents a potential hazard for humans within healthcare facilities. It is possible to contain its spread through continuous disinfection systems and the correct management and maintenance of the systems. The hygienic and sanitary quality of the water cannot be ignored in an evaluation of the management and energy costs. The Fondazione Policlinico Universitario A. Gemelli IRCCS in Rome has installed the “ME.SI. MR ACS” (MEthod of SavIngs Maximum eneRgy for hot water) device, which allows the system to activate, when necessary, avoiding continuous water recirculation. The objectives of this study are to evaluate the health and hygiene quality of the hospital water network and to evaluate the thermal and electrical energy savings and chlorine dioxide consumption, with and without this device in operation. This study involved three phases of microbiological sampling in the facility under study: ME.SI. MR ACS device installed but not running, with the boilers’ setpoint temperature at 60 °C; device running with the boilers’ setpoint temperature at 60 °C; and device in operation with the boilers’ setpoint temperature at 45 °C. The microbiological analyses were carried out in accordance with the ISO standard. The data show a constant absence of Legionella spp. in all samples. The application of ME.SI. MR ACS on the hot water recirculation circuit leads to a reduction in the daily consumption of electrical and thermal energy of 68.6% and 48.6%, respectively, for a savings of approximately EUR 23,000/year per circuit. Furthermore, with the device in operation, there is a 50% reduction in the chlorine dioxide consumption with a savings of EUR 11,500/year. ME.SI. MR ACS guarantees thermal and electrical energy savings associated with a reduction in chlorine dioxide consumption, maintaining the hygienic and sanitary quality of the water network.Keywords
This publication has 19 references indexed in Scilit:
- Legionellosis risk—an overview of Legionella spp. habitats in EuropeEnvironmental Science and Pollution Research, 2022
- Sample size, power and effect size revisited: simplified and practical approaches in pre-clinical, clinical and laboratory studiesBiochemia Medica, 2021
- Environmental surveillance of Legionella spp. colonization in the water system of a large academic hospital: Analysis of the four–year results on the effectiveness of the chlorine dioxide disinfection methodScience of The Total Environment, 2019
- Legionnaires' diseaseThe Lancet, 2016
- Prevention of hospital-acquired legionellosisCurrent Opinion in Infectious Diseases, 2011
- Chlorine dioxide for Legionella spp. disinfection: a danger for cross-linked polyethylene pipes?Journal of Hospital Infection, 2011
- Effectiveness of different methods to control legionella in the water supply: ten-year experience in an Italian university hospitalJournal of Hospital Infection, 2011
- Effect of pipe corrosion scales on chlorine dioxide consumption in drinking water distribution systemsWater Research, 2008
- Legionnaires' DiseaseClinical Infectious Diseases, 1993
- An analysis of variance test for normality (complete samples)Biometrika, 1965