Ac and transient electric field distributions along a 380 kV V-string insulator
Authors:
- 1 June 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 1089084X,p. 399-403
Abstract
This paper presents the results of a study of the ac and the transient electric field distributions along a 380 kV V-string of glass cap-and-pin suspension insulators. The transmission tower, conductors and insulators are modeled in 3D, and COMSOL 4.2 is used for the finite element simulations. The insulators are modeled both for clean and for the polluted cases. The pollution layer is modeled by a wet conductive layer of 2 mm thickness on the insulator surface and the conductivity of the layer is varied between 10-8 to 1.0 S/m. The permittivity of the pollution layer is assumed to be 81. Clean, full pollution and partial pollution cases are taken into consideration. The effects of corona rings on the field distributions are also investigated by 3D simulations.Keywords
This publication has 15 references indexed in Scilit:
- 380 kV corona ring optimization for AC voltagesIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Practical Cases of Electric Field Distribution Along Dry and Clean Nonceramic Insulators of High-Voltage Power LinesIEEE Transactions on Power Delivery, 2007
- Electric field calculation for HV insulators on the head of transmission tower by coupling CSM with BEMIEEE Transactions on Magnetics, 2006
- Impulse flashover performance of semiconducting glazed station insulator under icing conditions based on field calculations by finite-element methodIEE Proceedings - Generation, Transmission and Distribution, 2005
- Simulation of voltage distribution calculation methods over a string of suspension insulators2004
- Electric-field calculation for HV insulators using domain-decomposition methodIEEE Transactions on Magnetics, 2002
- Calculation of electric field and potential distribution along nonceramic insulators considering the effects of conductors and transmission towersIEEE Transactions on Power Delivery, 2000
- Solution of low frequency complex fields in polluted insulators by means of the finite element methodIEEE Transactions on Dielectrics and Electrical Insulation, 1997
- Electric field calculation for an axially-symmetric insulator with surface contaminationIEEE Transactions on Dielectrics and Electrical Insulation, 1994
- Power frequency and impulse field calculation around a HV insulator with uniform or nonuniform surface pollutionIEEE Transactions on Electrical Insulation, 1993