Influence of Non-Uniform Airflow on Two-Phase Parallel-Flow Heat Exchanger in Data Cabinet Cooling System
Open Access
Abstract
The energy consumption of data center cooling systems is rapidly increasing, necessitating urgent improvements in cooling system performance. This study investigates a pump-driven two-phase cooling system (PTCS) utilizing a parallel-flow heat exchanger (PFHE) as an evaporator, positioned at the rear of server cabinets. The findings indicate that enhancing the vapor quality at the PFHE outlet improves the overall cooling performance. However, airflow non-uniformity induces premature localized overheating, restricting further increases in vapor quality. For PFHEs operating with a two-phase outlet condition, inlet air temperature non-uniformity has a relatively minor impact on the cooling capacity but significantly affects the drop in pressure. Specifically, higher upstream air temperatures increase the pressure drop by 7%, whereas higher downstream air temperatures reduce it by 7.7%. The implementation of multi-pass configurations effectively mitigates localized overheating caused by airflow non-uniformity, suppresses the decline in cooling capacity, and enhances the operational vapor quality of the cooling system.Keywords
Funding Information
- Xiang Yang Solergy Technology Co., Ltd.
This publication has 51 references indexed in Scilit:
- Collision modeling approach and transient response mechanism of ring-ribbed cylindric shells for underwater vehiclesApplied Mathematical Modelling, 2024
- Machinability evolution of gas–liquid-solid three-phase rotary abrasive flow finishingThe International Journal of Advanced Manufacturing Technology, 2023
- Comparison of detached eddy simulation and standard k—ε RANS model for rack-level airflow analysis inside a data centerBuilding Simulation, 2022
- Research on the thermal performance of rack-level composite baffle diversion system for data centreEnergy Efficiency, 2020
- Experimental study and analytical modeling of thermosyphon loop for cooling data center racksHeat and Mass Transfer, 2019
- A review on airflow management in data centersApplied Energy, 2019
- Experimental study of the self-regulating performance of an R744 two-phase thermosyphon loopApplied Energy, 2017
- Experimental study on the thermal characteristics of micro channel separate heat pipe respect to different filling ratioApplied Thermal Engineering, 2016
- Effect of non-uniform air velocity distribution on evaporator performance and its improvement on a residential air conditionerApplied Thermal Engineering, 2012
- A simple friction pressure drop correlation for two-phase flow in pipesChemical Engineering and Processing - Process Intensification, 1986