Analysis of Characteristic Quantity of Incipient Fault of Medium Voltage Cable Joints in Water-Logged Environment Based on Fluid Characteristics
- 16 July 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 73 (00189456) , 1-12
Abstract
The incipient fault of a medium-voltage cable joint in a water-logged environment occurs before the permanent fault. Monitoring it can help prevent loss through the permanent fault. However, the characteristics of the incipient fault remain largely unknown. In this article, we report on the experimental simulation of an incipient fault according to actual operating scenarios and the measurement of both nonelectrical and electrical characteristics of the incipient fault. We then divide the incipient fault into three phases and further divide the start phase into three secondary phases, namely those relating to the predischarge, episodic discharge, and substable discharge (SSD). The dynamic characteristic of the liquid electrode in the incipient fault reveals that there is a certain stability when the SSD phase appears, which is considered the stage in which characteristics of the incipient fault can be extracted. The time-domain characteristics of the fault are somewhat unclear, while the harmonic content in the stage of the SSD is obviously clear and hardly changes with the further occurrence of incipient faults. This distinctive characteristic appears multiple times between the first incipient fault and the permanent fault and can be used to capture the appearance of incipient faults.Keywords
Funding Information
- National Natural Science Foundation of China (52077133)
This publication has 24 references indexed in Scilit:
- New experimental study on the DC flashover voltage of polymer insulators: combined effect of surface charges and air humidityHigh Voltage, 2019
- Electrowetting-based enhancement of droplet growth dynamics and heat transfer during humid air condensationInternational Journal of Heat and Mass Transfer, 2019
- The influence of surface charge accumulation on flashover voltage of GIS/GIL basin insulator under various voltage stressesInternational Journal of Electrical Power & Energy Systems, 2019
- Deformation and motion behavior of droplets in a non-uniform electric field2015
- Vibration of a water droplet on a polymeric insulating material subjected to AC voltage stressIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Influence of the water surface on the glow-to-spark transition in a metal-pin-to-water electrode systemPlasma Sources Science and Technology, 2008
- Breakdown between water drops on wet polymer surfaces2002
- Influence of thermal cycling on the cable-joint interfacial pressure2002
- Prevention of underground cable splice failures2002
- Ageing mechanisms and diagnostics for power cables - an overviewIEEE Electrical Insulation Magazine, 2001