Ke Wang
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Ke Wang has a total of 7 co-authors. Here are the top co-authors by number of shared publications:
- Xiuchen Jiang
Shanghai Jiao Tong University
4 shared publications - Yadong Liu
Shanghai Jiao Tong University
4 shared publications - Yingjie Yan
School of Electrical Engineering, Shanghai Jiao Tong University, Shanghai, China
4 shared publications - Zhipeng Yu
Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai, China
2 shared publications - Zihan Cong
Department of Electrical Engineering, Shanghai Jiao Tong University, Shanghai, China
2 shared publications - Dong Liu
Shanghai Jiao Tong University
1 shared publication
Latest Publications
- 17 October 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32 (3) , 1827-1836
Dynamic Resistance Characteristics of an Incipient Fault of a Medium-Voltage Cable Joint in a Water-Logged Environment
The internal flashover of a medium-voltage cable joint in a water-logged environment seriously affects the reliability of distribution networks. Monitoring an Incipient Fault can help prevent a power failure caused by a permanent fault. However, there have been few studies of the development and characteristics of the Incipient Fault. In this study, we experimentally simulated an Incipient Fault in a medium-voltage cable joint in a water-logged environment according to actual operating scenarios, and measured both non-electrical characteristics, namely insulation erosion, displacement and deformation of water electrode, and electrical characteristics, namely current and resistance changes, during the fault process. The results showed that the Incipient Fault underwent long-term accumulation, while its short-term characteristics did not change considerably. The fault resistance characteristic was made up by the water electrode, the erosion trace, and arc resistance in series, and fault characteristics were little affected by the external circuit like transmission line. Then, we selected two typical scenarios in which the first fault and erosion trace penetrated the insulation, and analyzed the time-domain characteristics of the magnitude and variation of the resistance values of the water, erosion trace, and arc in the Incipient Fault. The results showed that arc resistance played a major role in the fault current at the beginning and end of the fault, and water played a major role in the middle stage. During the fault process, the current amplitude showed the following trend: rising—small fluctuations—falling. As fault damage accumulated, the influence of erosion traces on the fault characteristics became larger. When the erosion traces penetrated the insulation surface, a permanent fault would be caused.
- 17 October 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32 (3) , 1827-1836
Dynamic Resistance Characteristics of an Incipient Fault of a Medium-Voltage Cable Joint in a Water-Logged Environment
The internal flashover of a medium-voltage cable joint in a water-logged environment seriously affects the reliability of distribution networks. Monitoring an Incipient Fault can help prevent a power failure caused by a permanent fault. However, there have been few studies of the development and characteristics of the Incipient Fault. In this study, we experimentally simulated an Incipient Fault in a medium-voltage cable joint in a water-logged environment according to actual operating scenarios, and measured both non-electrical characteristics, namely insulation erosion, displacement and deformation of water electrode, and electrical characteristics, namely current and resistance changes, during the fault process. The results showed that the Incipient Fault underwent long-term accumulation, while its short-term characteristics did not change considerably. The fault resistance characteristic was made up by the water electrode, the erosion trace, and arc resistance in series, and fault characteristics were little affected by the external circuit like transmission line. Then, we selected two typical scenarios in which the first fault and erosion trace penetrated the insulation, and analyzed the time-domain characteristics of the magnitude and variation of the resistance values of the water, erosion trace, and arc in the Incipient Fault. The results showed that arc resistance played a major role in the fault current at the beginning and end of the fault, and water played a major role in the middle stage. During the fault process, the current amplitude showed the following trend: rising—small fluctuations—falling. As fault damage accumulated, the influence of erosion traces on the fault characteristics became larger. When the erosion traces penetrated the insulation surface, a permanent fault would be caused.
- 2 September 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32 (2) , 1228-1237
Cumulative Damage Effect of the Pin-Type Porcelain Insulator Incipient Fault in Resonant Grounded Distribution Networks
Cracked porcelain insulators will experience discharges with self-clearing characteristics due to the influence of rainwater, called porcelain insulator incipient fault (PIIF). Frequent occurrences of the PIIF can cause irreversible cumulative damage to the cracked porcelain insulator, eventually leading to a permanent grounding fault. The cumulative damage effects on the porcelain walls caused by PIIF with different numbers of occurrences and different discharge energies were investigated in this article via theoretical analysis and physical experiments. The results indicate that when the discharge energy of PIIF is generally below 15 J, the cumulative rate of damage to the porcelain walls is so slow that it can be almost ignored. When the discharge energy is mainly distributed in the range of 15 J to 35 J, the surfaces of the porcelain walls will develop concave discharge traces, and the depth and width of these traces increase with increasing occurrence number and discharge energy of the PIIF. When PIIF with discharge energy exceeding 35 J occurs several times, a permanent grounding fault will occur soon.
- 2 September 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32 (2) , 1228-1237
Cumulative Damage Effect of the Pin-Type Porcelain Insulator Incipient Fault in Resonant Grounded Distribution Networks
Cracked porcelain insulators will experience discharges with self-clearing characteristics due to the influence of rainwater, called porcelain insulator incipient fault (PIIF). Frequent occurrences of the PIIF can cause irreversible cumulative damage to the cracked porcelain insulator, eventually leading to a permanent grounding fault. The cumulative damage effects on the porcelain walls caused by PIIF with different numbers of occurrences and different discharge energies were investigated in this article via theoretical analysis and physical experiments. The results indicate that when the discharge energy of PIIF is generally below 15 J, the cumulative rate of damage to the porcelain walls is so slow that it can be almost ignored. When the discharge energy is mainly distributed in the range of 15 J to 35 J, the surfaces of the porcelain walls will develop concave discharge traces, and the depth and width of these traces increase with increasing occurrence number and discharge energy of the PIIF. When PIIF with discharge energy exceeding 35 J occurs several times, a permanent grounding fault will occur soon.
- 16 July 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 73 (00189456) , 1-12
Analysis of Characteristic Quantity of Incipient Fault of Medium Voltage Cable Joints in Water-Logged Environment Based on Fluid Characteristics
The incipient fault of a medium-voltage cable joint in a water-logged environment occurs before the permanent fault. Monitoring it can help prevent loss through the permanent fault. However, the characteristics of the incipient fault remain largely unknown. In this article, we report on the experimental simulation of an incipient fault according to actual operating scenarios and the measurement of both nonelectrical and electrical characteristics of the incipient fault. We then divide the incipient fault into three phases and further divide the start phase into three secondary phases, namely those relating to the predischarge, episodic discharge, and substable discharge (SSD). The dynamic characteristic of the liquid electrode in the incipient fault reveals that there is a certain stability when the SSD phase appears, which is considered the stage in which characteristics of the incipient fault can be extracted. The time-domain characteristics of the fault are somewhat unclear, while the harmonic content in the stage of the SSD is obviously clear and hardly changes with the further occurrence of incipient faults. This distinctive characteristic appears multiple times between the first incipient fault and the permanent fault and can be used to capture the appearance of incipient faults.
- 16 July 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 73 (00189456) , 1-12
Analysis of Characteristic Quantity of Incipient Fault of Medium Voltage Cable Joints in Water-Logged Environment Based on Fluid Characteristics
The incipient fault of a medium-voltage cable joint in a water-logged environment occurs before the permanent fault. Monitoring it can help prevent loss through the permanent fault. However, the characteristics of the incipient fault remain largely unknown. In this article, we report on the experimental simulation of an incipient fault according to actual operating scenarios and the measurement of both nonelectrical and electrical characteristics of the incipient fault. We then divide the incipient fault into three phases and further divide the start phase into three secondary phases, namely those relating to the predischarge, episodic discharge, and substable discharge (SSD). The dynamic characteristic of the liquid electrode in the incipient fault reveals that there is a certain stability when the SSD phase appears, which is considered the stage in which characteristics of the incipient fault can be extracted. The time-domain characteristics of the fault are somewhat unclear, while the harmonic content in the stage of the SSD is obviously clear and hardly changes with the further occurrence of incipient faults. This distinctive characteristic appears multiple times between the first incipient fault and the permanent fault and can be used to capture the appearance of incipient faults.
- 22 March 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 39 (3) , 1840-1851
Study on the Mechanism and Electrical Characterization of the Distribution Porcelain Insulator Incipient Fault in the Non-Effectively Grounded System
The porcelain insulator incipient fault (PIIF) is a self-clearing discharge process caused by water entering the crack of the porcelain insulator. It will not result in a tripping operation but may evolve into a permanent grounding fault after multiple occurrences, leading to various types of accidents, such as wire breaks, power outages, fires, and personal electric shocks. This paper uncovered the mechanisms behind the initiation and evolution of the PIIF. Unique characteristics of the PIIF are analyzed from aspects such as the starting time, the power-resistance variation trend, and the fault duration. The characteristics were verified and supplemented by field experiments, and the influence of the insulator models, neutral grounding modes, and the number of discharges on these characteristics was analyzed. The results lay the foundation for the identification and pre-warning of PIIF.
- 22 March 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 39 (3) , 1840-1851
Study on the Mechanism and Electrical Characterization of the Distribution Porcelain Insulator Incipient Fault in the Non-Effectively Grounded System
The porcelain insulator incipient fault (PIIF) is a self-clearing discharge process caused by water entering the crack of the porcelain insulator. It will not result in a tripping operation but may evolve into a permanent grounding fault after multiple occurrences, leading to various types of accidents, such as wire breaks, power outages, fires, and personal electric shocks. This paper uncovered the mechanisms behind the initiation and evolution of the PIIF. Unique characteristics of the PIIF are analyzed from aspects such as the starting time, the power-resistance variation trend, and the fault duration. The characteristics were verified and supplemented by field experiments, and the influence of the insulator models, neutral grounding modes, and the number of discharges on these characteristics was analyzed. The results lay the foundation for the identification and pre-warning of PIIF.