Abstract
In order to provide fire-scene parameters for fire protection design and data support for fire safety management of waiting halls in high-speed railway stations, this study systematically investigated the combustion characteristics of single, two, and three massage chairs using an industrial calorimeter. The results showed the following: The change in heat release rate in the growth stage of the massage chairs’ combustion tests was consistent with the t2 fast fire (with a growth coefficient of 0.04689). The maximum HRR was 1.2 MW for the single-massage-chair combustion test, 2.5 MW for the two-massage-chairs combustion test, and 3.5 MW for the three-massage-chairs combustion test. In the full-scale massage chairs combustion test, setting a 6.0 m fire isolation zone could effectively serve the functions of fire prevention and heat insulation. Considering a certain safety margin, and with a safety factor of 1.5 adopted, it is recommended that a fire isolation zone with a width of 9.0 m be used in the waiting halls of high-speed railway stations, which provides a direct, actionable design basis for engineering practice.
Funding Information
  • CABR Fire Technology Co., Ltd. (20242501470738013, KSNQ243020)
  • China Railway Group Limited (20242501470738013, KSNQ243020)

This publication has 10 references indexed in Scilit: