Abstract
This paper discusses the effects of an incorrectly measured DC link voltage in a synchronous drive system. As the investigations show, the control algorithm can become unstable when the measured value for the DC link voltage is much smaller than the actual value. Therefore, this paper also presents two approaches for estimating the DC link voltage based on the measured currents, the motor speed and the duty cycle. If measured and estimated values of the DC link voltage deviate too much from each other, a fault diagnosis system detects this fault and enables different flags based on the fault scenario. The flags are then used to reconfigure the control algorithm, so that instead of the measured current its estimated value is used. The analysis shows the need for the reconfiguration of a faulty DC link voltage measurement and the experimental results demonstrate the effectiveness of the approach.