Adaptive Active Voltage-Type Arc Suppression Strategy Considering the Influence of Line Parameters in Active Distribution Network
- 20 July 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industrial Electronics
- Vol. 70 (5) , 4799-4808
Abstract
The reliable extinguishment of a single phase-to-ground arc is the key issue for safe and reliable operation in the distribution network. However, since the existing arc suppression methods are normally affected by the line parameters, the residual current (RC) at the grounding point still exists, then the grounding arc is hard to be extinguished reliably. Thus, an adaptive active voltage-type arc suppression (AAVAS) strategy that can reliably inhibit the RC at the grounding point is proposed in this article. First, the mechanism of the traditional voltage-type arc extinguishing method affected by the line parameters is proved, and the variation rules are given for the RC under different fault distances and grounding resistance. Second, the variation characteristics are analyzed for the faulty line current before and after arc extinguishing. On this basis, it is proposed to add the residual voltage compensation ring to the traditional voltage-type control strategy, which can effectively offset the influence of voltage drop on faulty-phase line impedance. Then, the Bode diagram analysis shows that the presented strategy performs well regardless of ground-fault conditions. Finally, the feasibility and effectiveness of the proposed AAVAS strategy are verified by the simulation and experiment results.Keywords
Funding Information
- National Natural Science Foundation of China (52077072)
- Hunan Science and Technology Loading Talent Plan (2019RS3014)
This publication has 25 references indexed in Scilit:
- Principle and Control Design of Active Ground-Fault Arc Suppression Device for Full Compensation of Ground CurrentIEEE Transactions on Industrial Electronics, 2017
- Principle and Design of a Single-Phase Inverter-Based Grounding System for Neutral-to-Ground Voltage Compensation in Distribution NetworksIEEE Transactions on Industrial Electronics, 2016
- Control method of an arc suppression device based on single-phase inverter2016
- A Novel Neutral Electromagnetic Hybrid Flexible Grounding Method in Distribution NetworksIEEE Transactions on Power Delivery, 2016
- Analysis of Temporary Overvoltages During Open-Phase Faults in Distribution Networks With Resonant GroundingIEEE Transactions on Power Delivery, 2014
- Residual current compensation for single-phase grounding fault in coal mine power networkInternational Journal of Mining Science and Technology, 2014
- Ground Fault Temporary Overvoltages in MV Networks: Evaluation and Experimental TestsIEEE Transactions on Power Delivery, 2012
- Bayesian Selectivity Technique for Earth Fault Protection in Medium-Voltage NetworksIEEE Transactions on Power Delivery, 2010
- Some Novel Techniques for Insulation Parameters Measurement and Petersen-Coil Control in Distribution SystemsIEEE Transactions on Industrial Electronics, 2009
- Prony's method: an efficient tool for the analysis of earth fault currents in Petersen-coil-protected networksIEEE Transactions on Power Delivery, 1995