Research on a Degradation Identification Method for GIS UHF Partial Discharge Sensors Based on S-Parameters
Open Access
Abstract
The ultra-high-frequency (UHF) detection method is highly accurate and has a fault localization function. At present, most gas-insulated switchgear (GIS) installations are equipped with online UHF monitoring devices to detect partial discharges. In order to ensure the accuracy of the detection results, UHF sensors need to be verified regularly. UHF sensors used for online monitoring are usually installed at the handhole of the GIS and cannot be removed. Measuring the laboratory verification indexes (e.g., equivalent height, dynamic range, etc.) of the sensors directly is very difficult. However, it is easier to measure S11 of the sensor for verification and S21 between it and the neighboring sensors by injecting power signals. Accordingly, this paper proposes a degradation identification method for GIS UHF sensors using a cross-comparison of S-parameters. When sensor sensitivity decreases, S11 increases while S21 decreases, both serving as effective indicators of performance degradation. In this study, the equivalent S-parameter network and the variation mechanisms of S11 and S21 during sensor verification were first analyzed. Normal and typically degraded sensor models were then constructed and coupled in different GIS structures for electromagnetic simulation. The simulation and on-site verification results show that S11 is mainly affected by the sensor’s intrinsic performance and installation conditions at the inspection port, whereas S21 is predominantly influenced by sensor performance and the propagation characteristics of the GIS structure. Through cross-comparison of S11 and S21 at corresponding positions across three phases, sensor aging or failure can be effectively identified, enabling rapid on-site verification without removing the sensors. The proposed method was successfully validated on actual GIS equipment at the China Southern Power Grid Research Institute. It exhibits high accuracy, efficiency, and strong engineering applicability, enabling the early detection of degraded sensors and providing valuable support for condition assessment and maintenance decision-making in GIS online monitoring systems.Keywords
Funding Information
- Southern Power Grid Scientific Research Institute Co., Ltd. (SEPRI-K243003)
This publication has 29 references indexed in Scilit:
- Simulation study of partial discharge UHF signal propagation characteristics in GISJournal of Physics: Conference Series, 2023
- Review on Partial Discharge Diagnostic Techniques for High Voltage Equipment in Power SystemsIEEE Access, 2023
- Numerical and Experimental Investigations on Influence of Internal Defect Parameters on Partial Discharge Induced UHF Signals in Gas Insulated SwitchgearIEEE Access, 2022
- Magnetic and electric antennas calibration for partial discharge charge estimation in gas-insulated substationsInternational Journal of Electrical Power & Energy Systems, 2022
- SF6Decomposed Component Analysis for Partial Discharge Diagnosis in GIS: A ReviewIEEE Access, 2022
- Detection, Classification and Location of Sources of Partial Discharges Using the Radiometric Method: Trends, Challenges and Open IssuesIEEE Access, 2021
- A Review: Partial Discharge Detection using UHF sensor on High Voltage EquipmentJournal of Physics: Conference Series, 2020
- GIS UHF Partial Discharge On-line Monitoring Device EvaluationIOP Conference Series: Materials Science and Engineering, 2018
- Partial discharge detection by extracting UHF signal from inner grading electrode of insulating spacer in GISIET Science, Measurement & Technology, 2018
- Status review on partial discharge measurement techniques in gas-insulated switchgear/linesElectric Power Systems Research, 2004