Abstract
Transformer-less grid-connected hybrid PV-wind energy systems offer higher efficiency but suffer from leakage current caused by parasitic capacitance and degradation in power quality. Therefore, an important research challenge is to design a multilevel inverter topology capable of minimizing leakage current while maintaining high power quality and efficient grid integration. To address the issue, two three-level converters, NPC1 and NPC2, are cascaded to achieve five-level transformer less inverter architecture. The effect of leakage current generated by the parasitic capacitance is studied with different PV and wind energy combinations with NPC1 and NPC2. A generalized inverter combination with LC-filters is presented to suppress the leakage current at the high switching frequency and fundamental frequency, satisfying the German standards DIN VDE 0126-1-1. The proposed inverter with LC-filters attenuates the pulse width modulation natured high-frequency voltage and improve the power quality and efficiency by enhancing the THD profile following the IEC 61707 and IEEE 1547-200 standards. The adopted control scheme maintains a constant dc-link voltage across the switches and enables the inverter to apply for high voltage applications. The proposed inverter dynamic and steady-state performance is compared with the different five-level combinations of PV and wind energy with NPC1 and NPC2. The results are experimentally validated in a hardware-in-the-loop FPGA based real-time digital simulator using OPAL-RT OP5700 as plant and dSPACE 1104 as controller.