Time-Domain Transmission Line Fault Location Method With Full Consideration of Distributed Parameters and Line Asymmetry
- 17 February 2020
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (6) , 2651-2662
Abstract
Accurate fault location reduces operating cost and outage time. This paper proposes a time-domain method to accurately locate faults in transmission lines, which only requires a very short data window (several milliseconds) during faults. First, the voltage distribution through the line during faults is accurately obtained by solving the matrix form partial differential equations using the proposed numerical scheme. The proposed numerical scheme is mathematically validated for the transmission line fault location problem, with the optimal selection of time and distance intervals to ensure stability and minimum solution error. Afterwards, the fault location is obtained via the extremum value of the voltage distribution. The method fully considers distributed parameters as well as asymmetry of the line. Extensive numerical experiments validated that (a) the proposed numerical scheme demonstrates advantages towards other numerical schemes; (b) the proposed method presents higher fault location accuracy compared to the existing method, independent of fault types, locations and impedances; and (c) the fault location accuracy is not sensitive towards fault inception angles, loading conditions, measurement errors and parameter errors. The proposed method works with relatively low sampling rates (80 samples per cycle) and is compatible with IEC 61850 standard in present digital substations.Keywords
Funding Information
- National Natural Science Foundation of China (51807119, 11601329)
- Shanghai Pujiang Program (18PJ1408100)
- Key Laboratory of Control of Power Transmission and Conversion
- Ministry of Education (2015AB04)
This publication has 21 references indexed in Scilit:
- Transient-Based Fault Location on Three-Terminal and Tapped Transmission Lines Not Requiring Line ParametersIEEE Transactions on Power Delivery, 2017
- A Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Lines Using the Distributed Parameter Line ModelIEEE Transactions on Power Delivery, 2014
- Impedance-based fault location in transmission networks: theory and applicationIEEE Access, 2014
- Parallel Transmission Lines Fault Location Algorithm Based on Differential Component NetIEEE Transactions on Power Delivery, 2005
- Travelling Wave Based Fault Location for Teed CircuitsIEEE Transactions on Power Delivery, 2005
- Fault Location on a Transmission Line Using Synchronized Voltage MeasurementsIEEE Transactions on Power Delivery, 2004
- Numerical Algorithm for Adaptive Autoreclosure and Protection of Medium-Voltage Overhead LinesIEEE Transactions on Power Delivery, 2004
- Fault location using the distributed parameter transmission line modelIEEE Transactions on Power Delivery, 2000
- Fault location using waveletsIEEE Transactions on Power Delivery, 1998
- Incorporation of terminal constraints in the FDTD analysis of transmission linesIEEE Transactions on Electromagnetic Compatibility, 1994