Evaluation of the Backflashover Performance of a 150 kV Overhead Transmission Line Considering Frequency- and Current-Dependent Effects of Tower Grounding Systems
Open Access
- 1 December 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 60 (2) , 2611-2620
Abstract
The influence of the frequency- and current-dependent response of tower grounding systems on evaluating the backflash over performance of a typical 150 kV overhead transmission line is investigated in this study. This is achieved by adopting different tower grounding system modeling approaches in ATP-EMTP simulations: 1) a simple resistor (constant resistance value), 2) the frequency dependent (FD) grounding system response with constant electrical properties of soil, 3) the FD response with FD soil properties, and 4) a soil ionization model. FD responses for concentrated and extended tower grounding systems are obtained via a hybrid method based on electromagnetic field analysis and circuit theory. Backflashover rate, BFR, is estimated by obtaining the minimum backflashover current of the line through ATP-EMTP simulations. Different first return-stroke currents of negative downward lightning flashes are employed in simulations, namely CIGRE WG 33.01 waveforms considering the statistical distributions of their parameters, recorded waveforms, and approximations of the latter with the CIGRE waveform. The impact of the lightning peak current distribution on BFR results is assessed. The evaluated backflashover performance is affected considerably by the FD tower grounding system response for extended systems, whereas by soil ionization for concentrated systems; for the latter, FD effects influence BFR mainly for low soil resistivity values.Keywords
Funding Information
- Hellenic Foundation for Research and Innovation
This publication has 43 references indexed in Scilit:
- Tower-foot grounding model for EMT programs based on transmission line theory and Marti's modelElectric Power Systems Research, 2023
- Estimation of the Minimum Backflashover Current and Backflashover Rate of a 150 kV Overhead Transmission Line: Frequency and Current-Dependent Effects of Grounding Systems2022
- Transient impedance of grounding grids with different soil models2021
- Computation of ground potential rise and grounding impedance of simple arrangement of electrodes buried in frequency-dependent stratified soilElectric Power Systems Research, 2021
- A 10-year study on the lightning activity in Italy using data from the SIRF networkAtmospheric Research, 2021
- Electromagnetic transient modeling of grounding electrodes buried in frequency dependent soil with variable water contentElectric Power Systems Research, 2020
- Evaluation of the impact of different frequency dependent soil models on lightning overvoltagesElectric Power Systems Research, 2018
- Practical model for tower earthing systems in lightning simulationsElectric Power Systems Research, 2018
- Modeling of lightning impulse behavior of long air gaps and insulators including predischarge current: Implications on insulation coordination of overhead transmission lines and substationsElectric Power Systems Research, 2016
- Numerical simulation grounding system buried within horizontal multilayer earth in frequency domainCommunications in Numerical Methods in Engineering, 2006