Probabilistic Risk Assessment of MV Insulator Flashover Under Combined AC and Lightning-Induced Overvoltages
Authors:
- 7 January 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 30 (4) , 1880-1888
Abstract
The effect of lightning-induced overvoltages is more profound in overhead distribution lines due to their limited height and low insulation level. Consequently, there is a high risk of line insulation flashover when exposed to lightning-induced overvoltages. This paper presents a probabilistic method to assess the risk of insulator flashover in medium-voltage overhead lines due to lightning-induced overvoltages. In order to accomplish this, a modified Gaussian cumulative distribution function has been used to predict the probability of single-phase, two-phase, and three-phase flashover of insulators under combined ac- and lightning-induced overvoltages. The validity of the modified probabilistic model is confirmed through experiments carried out in the high-voltage laboratory. Next, Monte Carlo simulations were performed on the simplified Rusck's model to generate the distribution of peak lightning-induced overvoltages. Finally, the risk of insulator flashover is calculated based on the distributions of lightning-induced overvoltages and insulator flashover voltages. The proposed procedure could be considered beneficial to select the optimum insulation level required against lightning-induced overvoltages by distinguishing between single-phase and multiphase flashover faults.Keywords
Funding Information
- Aalto Energy Efficiency Research Program
This publication has 21 references indexed in Scilit:
- Insulation characteristics of oil-immersed power transformer under lightning impulse and AC superimposed voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- A procedure to evaluate the risk of failure of distribution transformers insulation due to lightning induced voltages2013
- Field Analysis of the Occurrence of Distribution-Line Faults Caused by Lightning EffectsIEEE Transactions on Electromagnetic Compatibility, 2010
- Probabilistic model for MV spark-gap characteristics with lightning induced overvoltage superimposed on AC voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Probabilistic Evaluation of Optimal Location of Surge Arresters on EHV and UHV Networks Due to Switching and Lightning SurgesIEEE Transactions on Power Delivery, 2009
- Lightning Electromagnetic Field Coupling to Overhead Lines: Theory, Numerical Simulations, and Experimental ValidationIEEE Transactions on Electromagnetic Compatibility, 2009
- Failure Risk Prediction Using Artificial Neural Networks for Lightning Surge Protection of Underground MV CablesIEEE Transactions on Power Delivery, 2006
- Short tail lightning impulse behaviour of medium voltage line insulationIEEE Transactions on Power Delivery, 1999
- A damage mechanism: lightning-initiated fault-current arcs to communication cables buried beneath overhead electric power linesIEEE Transactions on Industry Applications, 1999
- Impulse breakdown superposed on ac voltage in XLPE cable insulationIEEE Transactions on Dielectrics and Electrical Insulation, 1996